40
No Error
code
Content
36 FE Heat
recovery
temperature
sensor
error
37
1FF DC
fan
A
error
2FF DC
fan
B
error
38
FP
DIP inconsistency of multiple water pumps(Power failure recovery required)
39
L0
Inverter module protection
40
L1
DC bus low voltage protection
41
L2
DC bus high voltage protection
42 L4 MCE
error
43 L5 Zero
speed
protection
44 L7 Phase
sequence
error
45
L8
Compressor frequency variation greater than 15Hz within one second protection
46
L9
Actual compressor frequency differs from target frequency by more than 15Hz protection
47 dF Defrosting
prompt
Содержание KJRM-120H