Install the indoor unit

1.Always mount the rear panel horizon-

tally.As the water drainage pipe at 
the left,this side should not be too 

2.Fix the rear panel on the selected location.

3.Be sure that the rear panel has been fixed firmly enough to withstand 

the weight of an adult of 60kg,furthermore,the weight should be

☆ 

Install the rear panel

☆ 

Install the piping hole

1.

Make the piping hole(¦Õ50) in the wall at a slight downward slant to

 

2.

Insert the piping-hole sleeve into the hole to prevent the connection

 

☆ 

Install the drain hose

1.For well draining, the drain hose shoule be placed

2.Do not wrench or bend the drain hose or flood its

end by water.

3.When the long drainage hose passing through indoor

on't soak in the water

Fig.2

☆ 

Install the connection pipes

tighten the flare nut of the connection pipes (Shown in P19"Install the connection

pipes")

Note:

Connect the connection pipes with the indoor unit 

Be careful in bending the connection pipes or you

 

If the tightening torque is too great in tightening 

☆ 

Electric wiring

1.Open the panel upwards.
2.Disassembly the fixing bolts of connection cover , shown in the Fig. at right side. 
3.power connecting wire cross through down to up from the bottom of case.

Fig.1

Bent

Wrenched

Install

 Part

cover of connection

connection power inside and 

high when adjusting the rear panel.it 

had better to adjust this side a little lower.

evenly shared each screw.

  

the outdoor side.

  

piping andwiring from being damaged when passing through the hole.

  at a downward slant.

  should wrap the insulation materials.

Connect the connection pipes with the relevant union pipes of the indoor unit and

 outside the unit

   

firstly and the outdoor unit secondly.

will damage the pipe.

the flare nuts, leakage will happen.

Содержание ASH-09AF

Страница 1: ... T I O N I N G Internet http www sinclair eu com E mail info sinclair eu com WALLMOUNTED SPLIT AIR CONDITIONER SINCLAIR OPERTIONAL MANUAL ASH 09AF ASH 12AF FLAT SERIE Before operation please carfully read this manual ...

Страница 2: ...ame and Function of Every Button of Wireless Remote Control 6 Operation Guide 8 Install Note Items 9 Install of Indoor Unit 12 Install of Outdoor Unit 14 Trial Run 17 Repair and Maintenance 18 When the unit cannot run normally 19 Structure Principle and Usage Install Part Repair Maintenance and ...

Страница 3: ...re and Function Panel Filter Air out cover plate Drainage hose Power plug Wireless remote control Air in Front grill of air outlet vent Heat Air out Outdoor unit Wire connection unit Indoor Air in Cool Dry Run Auto Connection pipe and wire ...

Страница 4: ... unit with wet hand for electric shock may occur vents or damage may occur Don t let cooled air blows body directly for too long and don t set indoor temp too low for it is If abnormal phenomenon occurs like burning odor etc cut off power supply first then contact Gree Service Center If abnormal continues the unit may be damaged and cause electric shock or fire Don t repair the unit yourself for i...

Страница 5: ...lows to monoxide poisoning may occur for heater or cooker directly Or carbon incomplete burn Chemical sprayer must be placed 1m away from both indoor and outdoor unit to prevent fire without repair unit may fall down Note if install chassis is damaged If the chassis is damaged and cause injury things may fall down and cause Don t stand or put things on the outdoor unit For people or injury Don t b...

Страница 6: ...pen windows or doors of the room for long time It would lower performance of the unit Temp dif of indoor and outdoors Don t pour water on the unit or wash it by water for malfunction or electric shock may occur Power hose of this unit adopts X type connection don t cut off or damage it and signal control wire If power hose or signal wire is damaged please have them changed by trained maintainer Th...

Страница 7: ...2500 3500 Heating Capacity W 2300 2700 3700 Rated Voltage 230V Rated Frequency 50Hz Cooling Heating Rated Power W 920 920 920 920 1440 1440 Cooling Heating Rated Currency A 4 4 4 4 6 26 6 26 Air Flow m 3 h 450 450 500 Name of Refrigerant and Charge Amount R410A 1 2kg R410A 1 35kg R410A 1 4kg Noise Indoor Outdoor dB A 38 52 38 53 40 54 Climate Type T1 Water proof Level IP 4 Electric Shork Proof Pro...

Страница 8: ...louvers start to rotate automatically and stop when repressed TEMP button SET TEMP increases 1 by pressing button once and decreases 1 by pressing button once At COOL mode operation SET TEMP can be selected from 16 to 30 At DRY mode operation SET TEMP can be selected from 16 to 30 At HEAT mode operation SET TEMP can be selected from 16 to 30 MODE button press this button to change the operation mo...

Страница 9: ...ton Press this button to set SLEEP operation And stop when repressed TIMER OFF button At operating press TIMER OFF button set OFF TIME in range of 0 to 24 hour to stop the unit automatically TIMER ON button At stopping press TIMER ON button set ON TIME in range of 0 to 24 hour at the interval of 0 5h to start the unit automatically 0 24h Timer cancellation 0 24h Timer cancellation Liquid crystal d...

Страница 10: ...t temp compressor stops and only indoor fan motor runs SET TEMP should be in range of 16 to 30 4 Press FAN button set fan speed 5 Press TEMP but ton set suitable SET TEMP 2 Press MODE button set operation mode 3 Press SWING button the louvers start to ro tate automatically and stop when repressed 1 Plug in press ON OFF button 1 0 is used in some models then air conditioner is turned on 5 REMOTE CO...

Страница 11: ...motor makes the louvers horizontal SET TEMP should be in range of 16 to 30 4 Press FAN button set fan speed 5 Press TEMP but ton set suitable SET TEMP 1 Plug in press ON OFF button 1 0 is used in some models then air conditioner is turned on 2 Press MODE button set operation mode 3 Press SWING button the louvers start to rotate automatically and stop when repress it 6 REMOTE CONTROL OPERATION PROC...

Страница 12: ...emp it s at COOL mode SET TEMP should be in range of 16 to 30 3 Press SWING button the louvers start to ro tate automatically and stop when repress it 4 Press TEMP button set suitable SET TEMP 2 Press MODE button set operation mode Air speed couldn t be changed after the being set 1 Plug in press ON OFF button 1 0 is used in some models then air conditioner is turned on 7 REMOTE CONTROL OPERATION ...

Страница 13: ...EMP is 25 for COOL mode and 20 for HEAT mode 2 According to room temp micro computer can automatically set operation mode so as for best effect 1 Plug in Press ON OFF but ton 1 0 is used in some models then air conditioner is turned on 8 REMOTE CONTROL OPERATION PROCEDURE ...

Страница 14: ...TIME in range of 0 to 24 hour to stop the unit automatically 0 24h Timer cancellation TIMER ON button At stopping press TIMER ON button set ON TIME in range of 0 to 24 hour to start the unit automatically 0 24h Timer cancellation 1 0 is used in some models 9 REMOTE CONTROL OPERATION PROCEDURE ...

Страница 15: ...button set or op eration mode 3 Press SWING button the louvers start to rotate automatically and stop when repress 6 SLEEP button Press it to set SLEEP operation As the unit is cooling or drying if SLEEP operation is set SET TEMP would increase 1 in 1 hour and 2 in 2 hours As the unit is heating if SLEEP operation is set SET TEMP would decrease 1 in 1 hour and 2 in 2 hours 10 REMOTE CONTROL OPERAT...

Страница 16: ...s Remove batteries when the remote controller is not in use for a long time The remote control sig nal can be received at the distance of up to about 10m The lifetime of the bat teries is about one year The remote controller should be placed about 1m or more away from the TV or any other electric appliances Bad batteries are for bidden 1 Remove the cover 3 Re attach the cover 2 Insert the AAA batt...

Страница 17: ...from TV Hi fi and other appliances 7 Select where air filter can be taken out easily Outdoor unit 1 Select place where noise and airflow produced when exharsting will not annoy neighbours 2 Ensure well ventilation of outdoor unit 3 There is no obstruction that may impact air in and out nears outdoor unit 4 Install place should be able to stand weight and libration of outdoor unit and let the outdo...

Страница 18: ...section Power wire of unit min section ASH 07AF ASH 12AF 10A Earthing requirements 1 Air conditioner is type I appliance please do conduct reliable earthing measure 2 The yellow green wire in the unit is earth wire don t use it for other purpose or cut it Don t fix it by self tapping screw or electric shock may occur Water pipe Gas pipe Blowing pipe Where professional personnel considers it unreli...

Страница 19: ...oid the malfunction due to unprofessional installation Install Part When moving the units you must be guided by professional personnel Distance between unit and ceiling Distance between unit and wall Distance between unit and floor Air out side Distance between unit and wall Distance between unit and slider Air in side Distance between unit and wall Distance between unit and wall Air out side ...

Страница 20: ...hten the flare nut of the connection pipes Shown in P19 Install the connection pipes Note Connect the connection pipes with the indoor unit Be careful in bending the connection pipes or you If the tightening torque is too great in tightening Electric wiring 1 Open the panel upwards 2 Disassembly the fixing bolts of connection cover shown in the Fig at right side 3 power connecting wire cross throu...

Страница 21: ...plate on where it was and tighten screws 7 Cover panel Signal control wire only for heat pump units Fig 3 Install Indoor Unit 1 Please refer to the fig a and b for routing piping type of indoor unit When routing the piping wiring from the left or right side cut off the tailings of the pipe left from chassis of main unit as shown in fig 4 c 2 Cut off tailings 1 and 2 when connection pipe and power ...

Страница 22: ...gh as shown in fig 6 4 Ensure the install height of indoor unit is 2m or higher Right pipe Rear right pipe a Left pipe Rear left pipe b c Tailings 1 Tailings 2 Fig 4 Fig 5 Fig 6 Wrapping strap Coonection pipe Power connect wire Signal control wire 1 Aligh the flare of connection pipe to the joint flare of relative valve 2 Tighten the nuts on connection pipe forcibly then tighten ti by spanner as s...

Страница 23: ...x power connect wire by clamp to cooling and heating unit fix signal control wire too then connect the corresponding connector well 4 Ensure that the wiring is done well 5 Install handle tightened by 1 bolt NOTE Wrong wiring connection will lead to electric malfunction The lead between the joint and the fixed should be a little free when fixing it with wire clamp Signal control wire Only for cooli...

Страница 24: ... piping both indoor and outdoor by liquid soap or leak detector 9 If possible discharge air from valve core with a vacuum pump shown in FIg 9 Outdoor condensation drainage Fig 9 Fig 8 condensing water and defrosting water formed in the outdoor unit can be drained out reliably through the drain hose in the 25 hole on the base plate as shown in Fig 10 and joint the drain hose to the tie in Fig 10 Sc...

Страница 25: ...b When unit is running press ON OFF to stop unit from running Check after installation Items to be checked Is the installation firm enough Possible malfunction Unit may drop shake or emit noise Is leakage test done It may cause insufficient of cooling heating capacity Is heat insulation sufficient Condensation or water drop may occur Is drainage smooth Condensation or water drop may occur product ...

Страница 26: ... down the panel according to direction of direction of arrow 1 then take out the filter or water when the filter is dirty oil it can be 1 Uplift the panel a little bit from the direc tion of arrowhead 1 then insert the filter 2 Uplift the panel according to the direction 3 Insert the clamp A B C back to three the rotating shaft and cover the panel Installation of filter washed by warm water below ...

Страница 27: ... Don t attempt to repair the air condotioner by yourself it can cause an electric shock or fire please check the following items before asking for repair it can save your time and money Phenomenon Trouble shooting There s unusual smell blowing from the This is caused by the odors which give off from furniture and cigarette Compressor do not operate when Once the air conditioner is stopped it will ...

Страница 28: ...ing efficiency is bad Is SET TEMP suitable Is air inlet or outlet obstructed Are air filters dirty Is indoor fan speed set at low speed Is there any other heat source in Remote control is not available Remote control can t be used occasion disturbed or changing its functions freq sert it again to recover the operation If it is in the received scope or Check if the batteries are suffici ent or repl...

Страница 29: ...d when the unit is running Air switch or creepage protect switch often trips Other things or water poured into unit or wireless remote control carelessly Power hose and power plug are extremely hot Abnormal odor is produced when the unit is running Please contact Gree Service center if there is any problem Repair and Maintenance Indoor water leakage occurs ...

Страница 30: ...ANT CHARGE Pursuant to Regulation EC 842 2006 on certain fluorinated greenhouse gases in case of extra refrigerant charge it is compulsory to Fill in the label accompanying the unit inserting the factory quantity of refrigerant charge see the technical label the extra refrigerant charge and the total charge Apply the label next to the technical label applied on the unit For the split type air cond...

Страница 31: ...30 ...

Отзывы: