12.   FAULTS OF REMOTE CONTROLLER
       AND CAUSE

The unit
keep
starting up
and
shutting
down
frequently

The ref rigerant  is
excessive or
deficient.

Air or noncondens-
able gas exists in the
refrigerant loop.

The compressor fails.

The voltage is too
high or too low.

The ref rigerant  loop is
obstructed

Detect leak, and fill the
refrigerant of a correct
quantity

Make a vacuum again
and fill the refrigerant .

Repair or replace the
compressor.
Install a voltage
regulator.

Locate the causes and
replace thepart.

Cleanse the condenser

Cleanse the filter

Remove foreign matters
to keep well ventilated.

Close all windows and
doors.

Use curtains or jalousie
to obstructsunlight.

Reduce heat sources

The cooling effect of the
air conditioner is
deteriorated (but normal)

Detect leak, and fill the
refrigerant of a correct
quantity

The outdoor environ-
ment temperature is
lower than -7°C

The door or window is
not closed tightly

The refrigerant is leaked
or the replenishment is
deficient

Use a heating device.

Close doors and
windows properly

Dete ct leak, and fill
the ref rigerantof a
correct quantity.

The condenser  of the
outdoor unit or indoor
unit is too dirty

The filter is blocked

The intake orifice or
exhaust orifice of the
outdoor/indoor unit is
blocked

The door or window is
open

Directly exposed to
sunlight

Too many heat
sources

Too high outdoor
environment tempera-
ture

The refrigerant is
leaked or the
replenishment is
deficient

The
cooling
effect is
poor

The
heating
effect is
poor

Before requesting for maintenance or repair, inspect the
following:

Symptom

The wind
speed
cannot be
shifted

Check item

The shift function cannot be set

cause

Check whether the
mode marked on the
screen is AUTO

Check whether the
mode marked on the
screen is DEWET

When you  select the
AUTO mode, the
indoor unit will select
“AUTO” for the air
speed automatically

When you  select the
DEWET mode, the
indoor unit will select
“AUTO” for the air
speed
automatically.The aie
speed is selectable
only in
the“cooling”,“heating”
and “supply air” mode

Symptom

After a while,
the ON/OFF
display
disappears

After a while,
the
TIMING ON
display
disappears

Check item

The display disappears

cause

Check whether the time
set on the timer has
expired

Check whether the time
set on the timer has
expired

The air conditioner
stops running
because the set time
has expired

When it comes to the
set time of starting
operation of the air
conditioner,the air
conditionerwill start
running automati-
cally, and the
corresponding display
will disappear.

Symptom

When you
press

ON/OFF

button, the
remote
controller
signal
cannot be
transmitted

Check item

The transmitting symbol

”does not blink

cause

Check whether the
batteries of remote
controller are low

When the batteries
are exhausted, the
signals cannot be
transmitted

Symptom

The
temperature
indicator
does not
light up

Check item

The temperature indicator dose not light up

cause

Check whether the
mode narked on the
screen is Supply Air

In the  Supply Air
mode, the temperature
cannot be set

Содержание ASDH-96AI

Страница 1: ...HIGH STATIC PRESSURE DUCT SERIE ASDH 96AI USER S MANUAL EN ...

Страница 2: ... Original instructions IMPORTANT NOTE Read this manual carefully before installing or operating your new air conditioning unit Make sure to save this manual for future reference ...

Страница 3: ... local government for information regarding the connection systems available If electrical appliances are disposed of in landfills or dumps hazardous substances can leak into the groundeater and get into the food chain damaging your health and well being To prevent refrigerant leak contact your dealer When the system is installed and runs in a small room it is required to keep the concentration of...

Страница 4: ...ade by children without supervision DISPOSAL Do not dispose this product as unsor ted municipal waste Collection of such waste sepa rately for special treatment is necessary Contact you local government for information regarding the collection systems available If electrical appliances are disposed of in landfills or dumps hazardous substances can leak into the groundwater and get into the food ch...

Страница 5: ...apacity of cooling heating efficient and energy saving Innovative air supply which provides homogeneous condition ing of the room temperature Remote control or wire control function Low noise design the A weighted sound pressure level is below 70 dB The air outlet is laid out in the way you desire Use refrigerant to transmit cool heat directly which provides a high transmitting efficiency It is su...

Страница 6: ... described in the manual only Table 6 1 Safety precautions Do not let the indoor unit or remote controller moistened Otherwise electric short circuit or fire may occur Do not use or store flammable gases or liquids near the air conditioner e g hair styling jelly paint and gasoline Otherwise fire may occur Do not touch the deflector plate while the air deflector works Otherwise the fingers may be c...

Страница 7: ...ing 9 MALFUNCTION CODE OF OUTDOOR UNIT 1 When stand by LED displaying the amount of indoor units online which communicate with outdoor units 2 When operation LED displaying frequency value of compressor 3 When defrost LED displaying dF 4 The power cord type designation is H07RN F No Failure or Protection Type Fault Code Recovery Mode Display Function Instruction COMM Fault between DSP and chip COM...

Страница 8: ...ter startup since the compressor does not run the tempera ture of the indoor unit is too low See the chapter headed Cooling Heating Supply Air Operation Procedure The indoor unit gives out white aerosol This phenomenon may occur when the indoor relative humidity is too high and the unit runs in the cooling mode in a place where there is much oil mist or dust If the internal stain of the indoor uni...

Страница 9: ...rant is leaked or the replenishment is deficient The cooling effect is poor The heating effect is poor Before requesting for maintenance or repair inspect the following Symptom The wind speed cannot be shifted Check item The shift function cannot be set cause Check whether the mode marked on the screen is AUTO Check whether the mode marked on the screen is DEWET When you select the AUTO mode the i...

Страница 10: ...mally shut down the unit and cut off the power supply promptly Then contact the manfacturer distributor Report the model operation environment and fault information of the air conditioner in detail request for sending technicians to repair but do not fix it by yourself at your discretion 14 TROUBLE SHOOTING PRE DEF indicator cooling and heating type or fan only indicator cooling only type Infrared...

Страница 11: ......

Страница 12: ... unit is containing fluorinated gases included in the Kyoto protocol The maintenance and the liquidation must be carried out by qualified personnel Type of refrigerant R410A The composition of the cooling medium R410A 50 HFC 32 50 HFC 125 The quantity of the refrigerant please see the unit label The value GWP 2088 1 kg R410A 2 088 t CO2 eq GWP Global Warming Potential In case of quality problem or...

Отзывы: