Symptom 4: Noise of air conditioners cooling  
 
Symptom 4.1: Indoor unit

 

 A continuous low "shah" sound is heard when the 

system is in cooling operation or at a stop.

 

When the drain pump (optional accessories) is in 
operation,this noise is heard.

 

 A "pishi-pishi" squeaking sound is heard when the 

system stops after heating operation.

 

Expansion and contraction of plastic parts caused by 
temperature change make this noise.

 

 
Symptom 4.2: Indoor unit, outdoor unit

 

 A continuous low hissing sound is heard when the 

system is in operation.

 

This is the sound of refrigerant gas flowing through both 
indoor and outdoor units.

 

A continuous low hissing sound is heard when the system 
is in operation.

 

This is the sound of refrigerant gas flowing through both 
indoor and outdoor units.

 

 A hissing sound which is heard at the start or 

immediately after stopping operation or defrost operation.

 

This is the noise of refrigerant caused by flow stop or flow 
change.

 

 
Symptom 4.3: Outdoor unit

 

 When the tone of operating noise changes. This noise is 

caused by the change of frequency.

 

 
Symptom 5: Dust comes out of the unit

 

 When the unit is used for the first time in a long time. 

This is because dust has gotten into the unit.

 

Symptom 6: The units can give off odors

 

 The unit can absorb the smell of rooms, furniture, 

cigarettes, etc., and then emit it again.

 

 
Symptom 7: The outdoor unit fan does not spin.

 

 During operation. The speed of the fan is controlled in 

order to optimize product operation.

 

8. TROUBLESHOOTING 

8.1 Troubles and causes of air conditioner

 

If one of the following malfunctions occur, stop operation, 
shut off the power, and contact with your dealer.

 

  The operation lamp is flashing rapidly (5Hz).

 

This lamp is still flashing rapidly after turn off the power 
and turn on again. (See in Table 8-1)

 

 Remote controller receives malfunction or the button 

does not work well.

 

 A safety device such as a fuse, a breaker frequently 

actuates.

 

 Obstacles and water enter the unit. 

 Water leaks from indoor unit.

 

 Other malfunctions.

 

If the system does not properly operate except the above 
mentioned cases or the above mentioned malfunctions is 
evident, investigate the system according to the following 
procedures. (See in Table 8-2)

 

 
8.2 Troubles and causes of remote controller

 

Before asking for serving or repairing, check the following 
points. (See in Table 8-3)

 

 

 

NO. 

Malfunction 

running lamp 

timer lamp 

defrosting lamp 

alarm lamp 

display (nixie 

tube) 

In-outdoor unit communication checking 
channel is abnormal 

Quick-flash 

  

Quick-flash 

  

E1 

Room temperature sensor checking 
channel is abnormal 

  

Quick-flash 

  

  

E2 

Evaporator sensor malfunction 

Quick-flash 

  

  

  

E3 

Condenser sensor malfunction 

  

  

Quick-flash 

  

E4 

Water pump temperature sensor 

  

  

  

Quick-flash E5 

Outdoor malfunction 

Quick-flash 

Quick-flash Quick-flash Quick-flash  E6 

EEPROM malfunction 

Quick-flash Quick-flash 

  

  

E7 

Water-level alarm malfunction 

  

  

  

Quick-flash E8 

DC motor speed out of control 

  

Quick-flash 

  

Quick-flash Eb 

10 

Outdoor unit low pressure malfunction 

Quick-flash Quick-flash Quick-flash 

  

Ed 

11 

Lifting panel communication checking 
channel is abnormal 

Quick-flash 

  

Quick-flash Quick-flash  F0 

12 

Lifting panel malfunction 

  

Quick-flash Quick-flash Quick-flash  F1 

13 

Lifting panel is not closed 

  

On Quick-flash 

Quick-flash 

F2 

14 

Refrigerant leakage detection malfunction 

Quick-flash 

  

  

Quick-flash EC 

Table 8-1 

Содержание ASC-60AN

Страница 1: ...USER S MANUAL ASC 60AN UNI ON OFF SERIES ...

Страница 2: ... Original instruction ...

Страница 3: ...splay panel Drain pipe Remote controller Air outlet Refrigerant pipe Air filter inside air in grill Air inlet Air inlet Air outlet NOTE All the pictures in this manual are for explanation purpose only They may be slightly different from the air conditioner you purchased depend on model The actual shape shall prevail ...

Страница 4: ... perform this work Do not dispose this product as unsorted municipal waste Collection of such waste separately for special treatment is necessary Do not dispose of electrical appliances as unsorted municipal waste use separate collection facilities Contact you local government for information regarding the connection systems available If electrical appliances are disposed of in landfills or dumps ...

Страница 5: ... including children with reduced physical sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety Children should be supervised to ensure that they do not play with the appliance If the supply cord is damaged it must be replaced by the manufacturer its service ...

Страница 6: ...emain open air will flow out of your room causing a decrease in the cooling or heating effect Never place objects near the air inlet or the air outlet of the unit It may cause deterioration in the effect or stop the operation Set the timer If you don t plan to use the unit for a long time please take the batteries from the remote controller When the power is on some energy will be consumed even if...

Страница 7: ... and connect the control box cables to the corresponding terminators of the main body Fig 6 1 Fig 6 2 Fig 6 3 Fig 6 4 7 FOLLOWING SYMPTOMS ARE NOT AIR CONDITIONER TROUBLES Symptom 1 The system does not operate The air conditioner does not start immediately after the ON OFF button on the romote controller is pressed If the operation lamp lights the system is in normal condition To prevent overloadi...

Страница 8: ...ur stop operation shut off the power and contact with your dealer The operation lamp is flashing rapidly 5Hz This lamp is still flashing rapidly after turn off the power and turn on again See in Table 8 1 Remote controller receives malfunction or the button does not work well A safety device such as a fuse a breaker frequently actuates Obstacles and water enter the unit Water leaks from indoor uni...

Страница 9: ... device Close doors and windows Check leakage and rightly recharge refrigerant Table 8 2 Symptoms Causes Solution The fan speed can not be changed Check whether the MODE indicated on the display is AUTO When the automatic mode is selected the air conditioner will automatically change the fan speed Check whether the MODE indicated on the display is DRY When dry operation is selected the air conditi...

Страница 10: ...3X2 housed in the rear part and protected by a cover 1 Remove the cover by pressing and sliding off 2 Remove the old batteries and insert the new batteries placing the and ends correctly 3 Reattach the cover by sliding it back into position NOTE When the batteries are removed the remote controller erases all programming After inserting new batteries the remote controller must be reprogrammed CAUTI...

Страница 11: ... LCD shows F2 Press the TEMP UP to control the faceplate up and press the TEMP DOWN to control the faceplate down Press any button to exit the faceplate setting state then the LCD back to the normal display TIMER ON Button Press this button to activate the Auto on time setting Each press will increase the time setting in 30 minutes increments up to 10 hours then at 1 hour increments up to 24 hours...

Страница 12: ... MODE display FAN mode FAN SPEED display Displays the selected fan speed AUTO HIGH MED if applicable and LOW Nothing displays when the fan speed is selected in AUTO speed When AUTO or DRY Mode is selected there will be no signals displayed TIMER display This display area shows the settings of the TIMER That is if only the Auto on time function is set it will display TIMER ON If only the Auto off t...

Страница 13: ...available 1 Press the MODE button to select COOL HEAT cooling heating models only or FAN mode 2 Press the TEMP button to set the desired temperature The temperature can be set within a range of 17 O C 30 O C in 1 O C increments 3 Press the FAN SPEED button to select the fan speed in four steps Auto Low Med or High 4 Press the ON OFF button to start the air conditioner NOTE In the FAN mode the sett...

Страница 14: ...o 24 hours 3 After setting the TIMER ON there will be a one half second delay before the remote controller transmits the signal to the air conditioner Then after approximately another 2 seconds the signal h will disappear and the set temperature will re appear on the LCD display window To set the Auto off time 1 Press the TIMER OFF button The remote controller shows TIMER OFF the last Auto off set...

Страница 15: ...t to stop the air conditioner after you go to bed and start it again in the morning when you wake up or when you return home Example To stop the air conditioner 2 hours after setting and start it again 10 hours after setting 1 Press the TIMER OFF button 2 Press the TIMER OFF button again to display 2 0h on the TIMER OFF display 3 Press the TIMER ON button 4 Press the TIMER ON button again to displ...

Страница 16: ...ELECTRIC SCHEMATIC DIAGRAM ASC 60AN indoor unit ASC 60AN outdoor unit ...

Страница 17: ... 5MPa SUCTION INDOOR MODEL ASC 60AN COOLING CAPACITY 14 9kW HEATING CAPACITY 17 0kW 111 1kg R410A 3500g 7000W 19 0A 1 5MPa 4 2MPa SPLIT UNIVERSAL AIR CONDITIONER OUTDOOR UNIT OUTDOOR MODEL 380 415V 3N 50Hz IP 24 REFRIGERANT EXCESSIVE OPERATING PRESSURE WEIGHT OUTDOOR POWER SOURCE OUTDOOR UNIT RESISTANCE CLASS DISCHARGE ASC 60AN SUCTION RATED INPUT RATED CURRENT RATING LABEL ...

Страница 18: ... A higher G lower kW Air Conditioner 3015 14 95 2 48 E 55 17 A B C D E F G ASC 60AN ASC 60AN Manufacturer Outside Unit Inside Unit Energy A B C D E F G More efficient Less efficient Noise dB A re 1 pW Further information is contained in product brochures Norm EN 14511 Air conditioner Energy Label Directive 2002 31 EC Annual energy consumption kWh in cooling mode kW Actual consumption will depend o...

Страница 19: ......

Страница 20: ...s located INFORMATION CONCERNING USED REFRIGERANT MEDIUM This unit is containing fluorinated gases included in the Kyoto protocol The maintanance and the liquidation must be carried out by qualified personel Type of refrigerant R410A The composition of the cooling medium R410A 50 HFC 32 50 HFC 125 The quantity of the refrigerant please see the unit label The value GWP 2088 GWP Global Warming Poten...

Отзывы: