10. Troubleshooting
10.1 Confirm below 2 points before any failures occurred
(1) Confirm power supply is OK
Check the plug of power line is normal energized and work.
(2) Confirm power voltage
Make sure the voltage is between normal range, if exceed the range, the unit may abnormally runs.
AC 220-240+/-10%
10.2 Error Code
Please see the blow failure contents and repair methods when the unit is energized or the error code occurred
during the unit runs.
Failure Display
Code
Failure Name
Dual-8
Display
Indicator Lamp
Repair Method
1
Environment temperature
sensor is open, short circuit.
F1
Cooling indicator lamp goes
out 3S blinks 1 time, and
lights up 0.5S goes out 0.5S
If loose, text resistance value if
normal by universal meter
2
Temperature sensor for
indoor pipe temperature is
open, short circuit.
F2
Cooling indicator lamp goes
out 3S blinks 2 times, and
lights up 0.5S goes out 0.5S
If loose, text resistance value if
normal by universal meter
3
Over-blow protection
H8
Over-blow indicator lamp goes
out 3S blinks 8 times
the indication of
instruction to discharge the water
of cha
s
sis.
Refer to
Содержание AMC-12AN
Страница 1: ...SERVICE MANUAL AMC 12AN MOBILE SERIES ...
Страница 2: ......
Страница 7: ...Outline and installation dimension Unit 460 Model AMC 12AN 4 Outline and installation Dimension ...
Страница 8: ...5 Refrigerant System Diagram HEAT EXCHANGE EVAPORATOR COMPRESSOR ...
Страница 9: ...Model AMC 12AN 6 1 Electrical wiring 6 Schematic Diagram ...
Страница 10: ...6 2 Printed Circuit Board Models AMC 12AN 6 2 1 Dispay board TOP VIEW BOTTOM VIEW ...
Страница 32: ...PARTS GUIDE AMC 12AN MOBILE SERIES ...
Страница 33: ... ...
Страница 34: ...9 1 Exploded View Model AMC 12AN ...