1.3

 

Sizing the M-Bus System 

Cable type 

 

Shielded telephone cable 0.5mm² 

 

Cable maximum capacitive load: 152 nF/km 

If you are using a cable with lower section, adapt the maximum length and the number of slaves 

Follow the instructions provided in the table to size the M-Bus system 

Type of plant 

Maximum 

distance 

Overall cable 

length 

Cross-section 

Number of 

devices 
(slaves) 

Max. 

transmission 

rate 

Small  residential 
buildings 

350 m 

1000 m 

0.8 mm

2

 

250 

9600 Baud 

Large  residential 
buildings 

350 m 

4000 m 

0.8 mm

2

 

250 

2400 Baud 

64 

9600 Baud 

Small complex 

1000 m 

4000 m 

0.8 mm

2

 

64 

2400 Baud 

Large 
developments 

…3000 m*

 

5000 m 

1.5 mm

2

 

64 

2400 Baud 

Direct vicinity 

…5000 m*

 

7000 m 

1.5 mm

2

 

16 

300 Baud 

Point-to-point 
connection 

…10000 m*

  10000 m 

1.5 mm

2

 

300 Baud 

*Shielded cabling required at a distance in excess of 1000 m (see EN13757-2). 

1.4

 

BUS signal specifications 

M-Bus system 

u.m. 

Condition 

Minimum  Typical 

Maximum 

Unit of 

measure

ment 

Number of devices per 
segment 

SIN.EQLC250 

 

250 

 

Transmission rate 

𝐶

𝑠𝑒𝑔𝑚𝑒𝑛𝑡

≤ 382𝑛𝐹

 

300 

2400 

9600  

Bd 

Bus Voltage (Master) 

U

M

 

IM=0…400mA

  30 

39 

42 

Bus Voltage (slave) 

U

S,R

 

𝐼

𝑆

≤ 1.5𝑚𝐴

 

30 

 

42 

Bus current (Master) 

I

M,V

 

SIN.EQLC250 

 

375 

mA 

Current (slave) 

I

S,R

 

US=30…42V

 

0.75 

1.2 

1.5 

mA 

 

 

 

 

Содержание EQUOBOX SIN.EQLC250

Страница 1: ...le Quer ce 11 1 3 06 0 83 B asti a Umbr a PG It al y T 3 9 0 7 5 8 0 1 16 0 4 F 3 9 0 7 5 8 0 14 6 0 2 w w w si napsitech it inf o sinapsitec h it EQUOBOX SIN EQLC250 M Bus Level Converter Adapter Rep...

Страница 2: ...BLE OF CONTENTS 1 M BUS OVERVIEW 3 1 1 DESCRIPTION of the M Bus System 3 1 2 Addressing 3 1 3 Sizing the M Bus System 4 1 4 BUS signal specifications 4 2 SIN EQLC250 INSTALLATION 5 2 1 Description of...

Страница 3: ...without requiring repeaters Large number of central units Detection of both battery powered and mains powered devices Automatic device recognition Vast array of systems and components available Differ...

Страница 4: ...of devices slaves Max transmission rate Small residential buildings 350 m 1000 m 0 8 mm2 250 9600 Baud Large residential buildings 350 m 4000 m 0 8 mm2 250 2400 Baud 64 9600 Baud Small complex 1000 m...

Страница 5: ...transformer or auxiliary power required The SIN EQLC250 unit can be used in different ways Connect up to 250 M Bus devices max 250 simply M Bus loads Can be connected with the M Bus web server of Equo...

Страница 6: ...er supply The power supply can be employed as follows To power the level converter 1 Level converter repeater 2 Power supply To power the M Bus web server SIN EQRTUxxx In the example below there is th...

Страница 7: ...rter 1 Pin 1 for main power 230 Vac 2 Pin 2 for main power 230 Vac 4 power supply 11 level converter 5 power supply 12 level converter C Power out 24Vdc for web server 15W D Electrical grounding 6 Pin...

Страница 8: ...pology and connection of the M Bus network M Bus technology allows good freedom of choice regarding network topology It is possible to connect the devices present in the plant according to a star line...

Страница 9: ...50 operation modes SIN EQLC250 can be used with M Bus communication interface for SIN EQRTUxxx datalogger Figure 6 or with a PC with EQUOBOX TOOLKIT software SIN EQSW1 Figure 7 or as a repeater extend...

Страница 10: ...network terminals 9 and 10 On Data is being received Off No data is being received Short Circuit The red LED indicates a short circuit on the bus very high traffic or a collision Overload The orange...

Страница 11: ...le to update the version of firmware in SIN EQLC250 if it is necessary Enter the default credentials User admin Password admin Select the Settings menu 1 Select the M Bus interface tab 2 If unchecked...

Страница 12: ...an excessive number of connected devices Check the wiring 3 The datalogger connected to the terminal does not detect some or all devices Check the correct bus connection between the datalogger and ter...

Страница 13: ...c terminals 6 and 7 on power supply DC 24 V max 15 VA INTERFACE RS 232 terminals A B and C Connections as master to PC using SIN EQUSB232 or to data logger Connect to a PC Terminal A RX PC data logger...

Страница 14: ...roduct design and assessments RoHS compliance DEGREE OF PROTECTION IP class IP20 per EN60529 Protection class II as per EN 62368 1 AMBIENT CONDITIONS Storage as per EN 60721 3 1 Climatic conditions Te...

Отзывы: