3.

 

Troubleshooting 

1) The device does not turn on (Power LED off) 
- Check with multimeter that the supply voltage to the terminals (11) and (12) is 

 40 V.

 

2) LED Overload on: 
- If the LED is on without any communication (RX and TX LEDs do not blink), there is an overload caused 
by  a  possible  short-circuits  between  the  two  poles  of  the  bus  or  from  an  excessive  number  of 
connected devices. Check the wiring. 
3) The datalogger connected to the terminal does not detect some or all devices: 
- Check the correct bus connection between the datalogger and terminal G of the SIN.EQLC250 
- Check with the multimeter that the voltage on devices not recognized is between 32Vdc-42Vdc 
- Verify that the communication settings of the M-Bus datalogger or the SW are compatible with the 
devices (speed of communication, addressing) 
4) The devices connected to the level converter in repeater mode do not communicate: 
- Check the correct power supply 
- Check the Run LED is on 
- Check that the Short Circuit LED is off 
- Check that the M-Bus network is connected to the G terminal of the SIN.EQLC250 
- Check the correct voltage in terminals G and H of the repeater which must be between 32 Vdc - 42 Vdc 

 

Содержание EQUOBOX SIN.EQLC250

Страница 1: ...le Quer ce 11 1 3 06 0 83 B asti a Umbr a PG It al y T 3 9 0 7 5 8 0 1 16 0 4 F 3 9 0 7 5 8 0 14 6 0 2 w w w si napsitech it inf o sinapsitec h it EQUOBOX SIN EQLC250 M Bus Level Converter Adapter Rep...

Страница 2: ...BLE OF CONTENTS 1 M BUS OVERVIEW 3 1 1 DESCRIPTION of the M Bus System 3 1 2 Addressing 3 1 3 Sizing the M Bus System 4 1 4 BUS signal specifications 4 2 SIN EQLC250 INSTALLATION 5 2 1 Description of...

Страница 3: ...without requiring repeaters Large number of central units Detection of both battery powered and mains powered devices Automatic device recognition Vast array of systems and components available Differ...

Страница 4: ...of devices slaves Max transmission rate Small residential buildings 350 m 1000 m 0 8 mm2 250 9600 Baud Large residential buildings 350 m 4000 m 0 8 mm2 250 2400 Baud 64 9600 Baud Small complex 1000 m...

Страница 5: ...transformer or auxiliary power required The SIN EQLC250 unit can be used in different ways Connect up to 250 M Bus devices max 250 simply M Bus loads Can be connected with the M Bus web server of Equo...

Страница 6: ...er supply The power supply can be employed as follows To power the level converter 1 Level converter repeater 2 Power supply To power the M Bus web server SIN EQRTUxxx In the example below there is th...

Страница 7: ...rter 1 Pin 1 for main power 230 Vac 2 Pin 2 for main power 230 Vac 4 power supply 11 level converter 5 power supply 12 level converter C Power out 24Vdc for web server 15W D Electrical grounding 6 Pin...

Страница 8: ...pology and connection of the M Bus network M Bus technology allows good freedom of choice regarding network topology It is possible to connect the devices present in the plant according to a star line...

Страница 9: ...50 operation modes SIN EQLC250 can be used with M Bus communication interface for SIN EQRTUxxx datalogger Figure 6 or with a PC with EQUOBOX TOOLKIT software SIN EQSW1 Figure 7 or as a repeater extend...

Страница 10: ...network terminals 9 and 10 On Data is being received Off No data is being received Short Circuit The red LED indicates a short circuit on the bus very high traffic or a collision Overload The orange...

Страница 11: ...le to update the version of firmware in SIN EQLC250 if it is necessary Enter the default credentials User admin Password admin Select the Settings menu 1 Select the M Bus interface tab 2 If unchecked...

Страница 12: ...an excessive number of connected devices Check the wiring 3 The datalogger connected to the terminal does not detect some or all devices Check the correct bus connection between the datalogger and ter...

Страница 13: ...c terminals 6 and 7 on power supply DC 24 V max 15 VA INTERFACE RS 232 terminals A B and C Connections as master to PC using SIN EQUSB232 or to data logger Connect to a PC Terminal A RX PC data logger...

Страница 14: ...roduct design and assessments RoHS compliance DEGREE OF PROTECTION IP class IP20 per EN60529 Protection class II as per EN 62368 1 AMBIENT CONDITIONS Storage as per EN 60721 3 1 Climatic conditions Te...

Отзывы: