CONNECTION DIAGRAM
Mains
Supply
Isolation
Switch
SECTION FOUR
OPERATION AND TESTING
WALK TEST PROCEDURE
The sensor will rotate from left to right, and tilt forward or backward. Adjust the sensor to point in
the required direction. (note diagram B)
The unit can be set up in daylight or at night. The adjustment knobs are factory set. Lux is set to
the ‘Moon’ setting and Time is set to a minimum. If not, set as shown in diagram G.
Max - turn knob clockwise, min - turn knob anticlockwise
Turn the power to the unit on. The lamp will illuminate for approximately 30 seconds. This
indicates the unit is wired correctly.
After approximately 30 seconds the light will turn off.
The unit is now in Test Mode.
The diagram below also shows the required connections for the addition of slave luminaires.
When adding slaves, be sure not to exceed the maximum switchable load (see Technical
Specifications).