WIRING
Single-phase SIMUBOX motors have been made to be exclusively wired with 1.5mm² diameter cables for the power
supply connection and with 0.75mm² diameter cables for the command connection.
Attach the cables to prevent contact with moving parts.
- The installer must ensure that the installation of the motorization complies with the electrical installation instructions
in force in the country of commissioning.
- Always make a loop on the power cable to prevent water penetration into the actuator.
- Cables passing through a metal wall must be protected and insulated by a sleeve or sheath.
- The motor casing must be connected to a rigid conduit.
- Use the traction stop.
- The connection of the power supply conductors must be carried out after the motor has been installed on its support.
- Cables have to be stripped on 8 mm.
Installation diagram:
S1
S2
S1
S2
5
L N
SAFETY BRAKE
Cde S1
Cde Com
Cde S2
N
2
3
4
1
1I
PI
2I
4
3
2
POWER SUPPLY
1
1
KEYSWITCH
1
2
3
4
The keyswitch has to be connected to the Ground if
it’s class 1.
There are 2 auxiliary contacts available which allow,
for example, to know if the door is in open or closed
position.
Outputs are made on a 3 terminal connector which is
fixed on the cover plate.
Outputs of auxiliary contacts on 3 terminal connector :
• 1 terminal Ri S1 for S1
• 1 terminal Ri Com for common
• 1 terminal Ri S2 for S2
Type of output: dry contacts normally open
Capacity: 1A under 24V
4.2 - Mounting of chain manual override
1. Remove the chain cover by
unscrewing the 4 screws.
2. Install the chain.
3. Pass the chain links in the
chain guide and in the notched
wheel by introducing them in.
4. Replace the cover.
i
Traction stop has to be used.
EN
4/5