REV070219
SimpliPhi Power, Inc. | 3100 Camino Del Sol | Oxnard, CA 93023, USA | (805) 640-6700 | [email protected] |
SimpliPhiPower.com
| 9 |
4.2
– PHI 3.8 General Settings with Victron
The general program settings for the PHI 3.8 Batteries with Victron products are outlined below.
Table 1.0 - Settings for SimpliPhi PHI 3.8 kWh 24V / 48V Battery w/Victron
General
10k Cycles
(80% DoD)
5k Cycles
(90% DoD)
3.5k Cycles
(100% DoD)
Battery Curve
Fixed
Capacity
1
(Ah)
151Ah
per PHI3.8 24V; (
302Ah
for 2,
453Ah
for 3)
75Ah
per PHI3.8 48V; (
150Ah
for 2,
225Ah
for 3)
Absorb Voltage (V)
27.2 / 54.4
27.2 / 54.4
28 / 56
Absorb Time
1 Hour
Float Voltage (V)
27 / 54 (typically Disable)
Discharge Voltage "LBCO" (V)
25.1 / 50.2
24.8 / 49.6
24 / 48
Re-Charge (V)
25.3 / 50.6
Max Discharge/Charge Current (C/2)
1
45A
per PHI3.8 24V; (
90A
for 2,
135A
for 3)
37.5A
per PHI3.8 48V; (
75A
for 2,
112.5A
for 3)
Peukert Expo
1.05
Charge Efficiency
95%
SoC when Bulk Finished
95%
Notes:
•
1. Per PHI 3.8 Battery
– These settings are calculated by multiplying the nominal per battery value times the #
of batteries.
•
Levels are typical @ 25°C and may need adjusting at temperature extremes.
•
When performing rapid deep charge/discharge cycles, the PHI Battery should be allowed to "rest" 15 minutes
in between.
•
Always refer to the SimpliPhi Power Manual and Warranty for the specific PHI Battery model.
4.3
– Victron BMV-700 Programming Settings
Table 2.0 - Settings for SimpliPhi PHI 3.8 kWh 48V Battery w/Victron BMV-700 Battery Monitor
Victron BMV-700 Settings
PHI 3.8 kWh 24V / 48V
Quick Start
Battery Capacity
1
(Ah)
151Ah per PHI3.8 24V; (302Ah for 2, 453Ah for 3)
75Ah per PHI3.8 48V; (150Ah for 2, 225Ah for 3)
Charged Voltage (V)
26.5 / 53.2
Tail Current (%)
4
Charge Detection Time (minutes)
1
Peukert Exponent
1.05
Charge Efficiency Factor (%)
98
Current Threshold (A)
0.1
Time to go Averaging Period (minutes)
3
Notes:
•
1. Per PHI 3.8 Battery
– These settings are calculated by multiplying the nominal per battery value times the #
of PHI Batteries.
•
Levels are typical @ 25°C and may need adjusting at temperature extremes.
•
When performing rapid deep charge/discharge cycles, the PHI Battery should be allowed to "rest" 15 minutes
in between.
•
Always refer to the SimpliPhi Power Manual and Warranty for the specific PHI battery model.
CAUTION:
When battery quantities change, the capacity current settings must to be reassessed.