background image

REV070219 

 

 

 

SimpliPhi Power, Inc. | 3100 Camino Del Sol | Oxnard, CA 93023, USA | (805) 640-6700 | [email protected] | 

SimpliPhiPower.com

 

|  9  |

 

 

4.2 

– PHI 3.8 General Settings with Victron 

The general program settings for the PHI 3.8 Batteries with Victron products are outlined below. 

Table 1.0 - Settings for SimpliPhi PHI 3.8 kWh 24V / 48V Battery w/Victron 

General 

10k Cycles 

(80% DoD) 

5k Cycles 

(90% DoD) 

3.5k Cycles 

(100% DoD) 

Battery Curve 

Fixed 

Capacity

1

 (Ah) 

151Ah

 per PHI3.8 24V; (

302Ah

 for 2, 

453Ah

 for 3) 

75Ah

 per PHI3.8 48V; (

150Ah

 for 2, 

225Ah

 for 3) 

Absorb Voltage (V) 

27.2 / 54.4 

27.2 / 54.4 

28 / 56 

Absorb Time 

1 Hour 

Float Voltage (V) 

27 / 54 (typically Disable) 

Discharge Voltage "LBCO" (V) 

25.1 / 50.2 

24.8 / 49.6 

24 / 48 

Re-Charge (V) 

25.3 / 50.6 

Max Discharge/Charge Current (C/2)

1

 

45A

 per PHI3.8 24V; (

90A

 for 2, 

135A

 for 3) 

37.5A

 per PHI3.8 48V; (

75A

 for 2, 

112.5A

 for 3) 

Peukert Expo 

1.05 

Charge Efficiency 

95% 

SoC when Bulk Finished 

95% 

 

Notes:  

 

1. Per PHI 3.8 Battery 

– These settings are calculated by multiplying the nominal per battery value times the # 

of batteries. 

 

Levels are typical @ 25°C and may need adjusting at temperature extremes. 

 

When performing rapid deep charge/discharge cycles, the PHI Battery should be allowed to "rest" 15 minutes 
in between. 

 

Always refer to the SimpliPhi Power Manual and Warranty for the specific PHI Battery model. 

4.3 

– Victron BMV-700 Programming Settings 

Table 2.0 - Settings for SimpliPhi PHI 3.8 kWh 48V Battery w/Victron BMV-700 Battery Monitor 

Victron BMV-700 Settings 

PHI 3.8 kWh 24V / 48V 

Quick Start 

Battery Capacity

1

 (Ah) 

151Ah per PHI3.8 24V; (302Ah for 2, 453Ah for 3) 

75Ah per PHI3.8 48V; (150Ah for 2, 225Ah for 3) 

Charged Voltage (V) 

26.5 / 53.2 

Tail Current (%) 

Charge Detection Time (minutes) 

Peukert Exponent 

1.05 

Charge Efficiency Factor (%) 

98 

Current Threshold (A) 

0.1 

Time to go Averaging Period (minutes) 

 

Notes: 

 

1. Per PHI 3.8 Battery 

– These settings are calculated by multiplying the nominal per battery value times the # 

of PHI Batteries. 

 

Levels are typical @ 25°C and may need adjusting at temperature extremes. 

 

When performing rapid deep charge/discharge cycles, the PHI Battery should be allowed to "rest" 15 minutes 
in between. 

 

Always refer to the SimpliPhi Power Manual and Warranty for the specific PHI battery model. 

CAUTION: 

When battery quantities change, the capacity current settings must to be reassessed.  

 

 

Содержание PHI 3.8

Страница 1: ...r PHI Battery Optimized Energy Storage Management for Residential Commercial Applications Utilizing Efficient Safe Non Toxic Energy Dense Lithium Ferrous Phosphate LFP Chemistry SIMPLIPHI POWER INC RE...

Страница 2: ...pliPhi storage technology eliminates operating temperature constraints toxic coolants and the risk of thermal runaway and fire Safe lithium ferrous phosphate No cobalt No hazards SimpliPhi s battery t...

Страница 3: ...oller Power Sizing 5 3 0 Victron BMV 700 Installation Setup 5 3 1 Standard Features 6 3 2 Installation Connections 6 3 3 Installation Quick Start Guide 7 3 4 Victron Available Interfaces 8 4 0 Program...

Страница 4: ...Based on tests and evaluations the following parameters refer to tables below have been established More information on Victron products can be found on their website https www victronenergy com More...

Страница 5: ...controller max 80A B PV 80A 37 5A 2 13 A properly sized PHI Battery bank based on available PV charge would have a minimum of 3 PHI Batteries This maximizes the use of available PV while ensuring the...

Страница 6: ...atteries on Apple or Android smartphones tablets Macbooks and other devices 3 2 Installation Connections Follow the instructions below to setup the BMV 700 CAUTION Connect the Negative Pole of the PHI...

Страница 7: ...each digit is selected iii Calculate total bank capacity based on number of PHI Batteries in the bank iv Example 75Ah x 3 Batteries 225Ah b Press setup for 2 seconds to enter other parameters of the B...

Страница 8: ...quired contact Victron Energy at sales victronenergy com or call Victron at 31 0 36 5359700 4 0 Program Settings for PHI Batteries In order to maintain the Warranty it is critical to ensure that the a...

Страница 9: ...may need adjusting at temperature extremes When performing rapid deep charge discharge cycles the PHI Battery should be allowed to rest 15 minutes in between Always refer to the SimpliPhi Power Manua...

Страница 10: ...6V 48V Voltage for Discharge 23A 50 2 49 6V 48V Voltage for Discharge 66A2 50 49 1V 47 5V MultiPlus Quattro Inverter Chargers 10k Cycles 80 DoD 5k Cycles 90 DoD 3 5k Cycles 100 DoD VE Configure Gener...

Страница 11: ...Current C 2 1 37 5A per PHI3 8 75A for 2 112 5A for 3 Default Charge Settings OFF Absorb Voltage 54 4V 54 4V 56V Absorb Time 1 Hour Float Voltage 54V Equalization Voltage 54V Auto Equalization OFF Tem...

Страница 12: ...50 1 49 5V 48V 2C2 49 7 49 1V 48V Restart Offset 1 2V Victron Default Absorption Voltage 54 4V FOR BACKUP ONLY SYSTEM Color Control GX Venus GX Settings Keep Batteries Charged Mode Optimized with Batt...

Страница 13: ...For your reference See PHI 3 8 kWh 48V Specifications sheet See PHI 3 8 kWh 48V 10 Year Warranty Failure to adhere to installation protocol will void Warranty 6 0 SimpliPhi Technical Support For techn...