REV070219
SimpliPhi Power, Inc. | 3100 Camino Del Sol | Oxnard, CA 93023, USA | (805) 640-6700 | [email protected] |
SimpliPhiPower.com
| 7 |
Figure 1.0 - BMV-700 Typical Installation
CAUTION:
Connect the Negative Pole of the PHI Battery last!
3.3
– Installation – Quick Start Guide
After installation / connection, on initial startup, the BMV-
700 “Setup Wizard” will automatically start. The
following steps should be used to initialize the meter.
1. BMV will automatically start the setup wizard.
a.
The scrolling text “Battery Capacity “will appear.
i.
Set the Ah capacity using the +/- buttons.
ii.
P
ressing “select” after each digit is selected.
iii.
Calculate total bank capacity based on number of PHI Batteries in the bank.
iv.
Example: 75Ah x 3 Batteries = 225Ah.
b.
Press “setup” for 2 seconds to enter other parameters of the BMV.
c.
Press “select” to access the desired parameter.
d. Use the +/- buttons to customize the settings.
e. For PHI 3.8 kWh Batteries,
set parameters per Table 1.0
below.
f.
Zero Current calibration: Disconnect the Negative cable between the load and shunt and
press
“select”.
g.
Synchronize: press “select”.
h. For any other settings, such as relay, temperature, or alarm settings, consult the BMV
Manual.
i.
Press “setup” to end the wizard.
The BMV should be setup for normal use at this time.
If additional assistance is required, contact Victron Energy at:
+31 (0)36 5359700.