This publication discusses the following topics: 
 

Topic

 

See Page

 

TrueAlert Is Wiring 

TrueAlert Is Class B Wiring 

TrueAlert Is Class A Wiring 

Mounting the TrueAlert Is Module 

Setting the TrueAlert Is Module Address 

 
 
 

 

                                   Figure 1. TrueAlert Is Module 

Warning:

   Make sure that all power is disconnected before starting the installation. 

 

Caution:

   Connect Wiring to terminals as shown.  Do not loop wires under terminals. 

Break wire runs to provide supervision of connections. Do not bring conduit 
through the rear of the electrical box. Strip lead insulation to 3/8” maximum. 

1.

 

At the electrical box, connect the contractor wire to the PORT 1/PORT 2 (+ and -) terminal of 
the TrueAlert Is Module. See figure 2 and 3, TrueAlert Is Class B and A 
Wiring. 

2.

 

Ensure that correct polarity is maintained across the ports. 

3.

 

Ensure that the CKT +’s or -’s are not crossed between ports. 

4.

 

Do not loop wires under the terminals. 

 
 

Installation instructions, Continued 

Installation instructions, Continued 

In this Publication 

TrueAlert Is 
Wiring 

Содержание TrueAlert Isolator+

Страница 1: ... of notification appliances provides addressable control and supervision of individual appliances and circuit wiring Appliances are operated over a single two wire notification appliance circuit TrueAlert Channel that allows T tapping Class B only The TrueAlert Isolator Module provides a means of containing the effects of a short circuit on the TrueAlert Channel to a single segment of wire as well...

Страница 2: ...wires under terminals Break wire runs to provide supervision of connections Do not bring conduit through the rear of the electrical box Strip lead insulation to 3 8 maximum 1 At the electrical box connect the contractor wire to the PORT 1 PORT 2 and terminal of the TrueAlert Isolator Module See figure 2 and 3 TrueAlert Isolator Class B and A Wiring 2 Ensure that correct polarity is maintained acro...

Страница 3: ...f wire protected by one or more Isolator modules limit the wire resistance to a maximum value of 1 5 ohms for a given line path The wire resistance is measured from the Controller s port to the furthest appliance in the protected segment Deviation from this limitation does not guarantee isolation for short circuits that are located greater than 1 5 ohms Figure 2 TrueAlert Isolator Class B Wiring I...

Страница 4: ...wiring connections are supervised and power limited 6 Powering the Isolator Module from an appliance power source less than 17 6 VDC or greater than 32 VDC may cause permanent damage to the module 7 The TrueAlert Isolator Module can be operated through the TrueAlert Addressable Controller the TrueAlert compatible FACP the 4009 IDNAC Repeater or the EPS IDNAC 8 The Isolator Module counts for 4 unit...

Страница 5: ... The TrueAlert Isolator Module uses terminals to connect to each wire point Each accepts 2 wires of gauges 12 through 18 AWG The terminal screws at TB1 accommodate both slotted and Philips drive Refer to the Field Wiring Diagrams or applicable installation manuals for detailed information on maximum wire run distance FigureTag FD4 769 02 Grounded Metal Electrical Box Electrical box 4 square 102 mm...

Страница 6: ...t Channel 4009 TrueAlert Addressable NAC Controller or TrueAlert compatible FACP only supports address codes 1 through 63 2 DIP switch in 1 position is ON while DIP switch in 0 position is OFF Table 1 TrueAlert Isolator Module DIP Switch Address Chart 0000 1000 0100 1100 0000 0 16 32 48 1000 1 17 33 49 0100 2 18 34 50 1100 3 19 35 51 0010 4 20 36 52 1010 5 21 37 53 0110 6 22 38 54 1110 7 23 39 55 ...

Отзывы: