background image

Features 

 

Individually addressed and controlled 
multi-candela V/O (visible only) notification 
appliances provide: 

 

Multi-candela xenon strobe with synchronized 1 Hz 
flash rate and with intensity 

programmable from the 

control panel

 or jumper selected as 15, 30, 75, or 

110 cd 

 

Advanced addressable notification controlled by 

IDNAC 

SLCs

 from Simplex

®

 4100ES fire alarm control panels 

with EPS/EPS+ power supplies (and 4009 IDNAC 
Repeaters) providing 

regulated 29 VRMS

 allowing 

strobes to operate with lower current even under 
battery backup 

 

Wiring supervision to each strobe allowing 
“T-tapped” connections for Class B circuits to 
simplify wiring (Class A circuits require in/out 
wiring) 

 

TrueAlert Device Reports

 at the control panel 

detailing appliance point ID, custom label, type, and 
candela setting (see sample on page 2) 

 

Magnet test diagnostics

 to assist checkout and testing 

of appliances and wiring 

 

Compatibility with ADA requirements 

 

Compatibility with legacy TrueAlert addressable 
systems for upgrade and replacement (see page 3) 

 

UL listed to Standard 1971 and ULC-S526*

 

LED indicator and magnet test feature: 

 

Appliance LED can be selected to display each polling 
cycle to indicate appliance supervision 

 

In diagnostic mode, the magnet test pulses the LED to 
indicate appliance address 

AND pulses to indicate the 

intensity selection

; a brief output of the strobe is also 

selectable to confirm operation 

Mechanical design features:  

 

Rugged, high impact, flame retardant ceiling mount 
thermoplastic housings are available in red or white 

 

Rear of housing does not extend into box and easily 
mounts to standard electrical boxes 

 

Mounting options include red wire guards and 
adapters for surface mounted electrical boxes 

 
 
*

    See page 2 for wire guard listings. This product has been approved by the California State 

Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health and Safety 

Code. See CSFM Listing 7125-0026:235 for allowable values and/or conditions concerning 

material presented in this document.

 

Accepted for use – City of New York Department of 

Buildings – MEA35-93E. Additional listings may be applicable; contact your local Simplex 

product supplier for the latest status. Listings and approvals under Simplex Time Recorder 
Co. are the property of Tyco Safety Products Westminster.  

 

 

 

Ceiling Mount Addressable V/Os 

Description 

 

Multi-Candela TrueAlert addressable strobes

 

provide convenient installation to standard electrical 
boxes. The strobe is individually addressed and 
individually controlled with power, supervision, and 
control supplied from a Simplex fire alarm control panel 
providing 

IDNAC

 Signaling Line Circuits (SLCs). (See 

compatibility list on page 3.)  

Strobe Application Reference 

 

Proper selection of visible notification is dependent on 
occupancy, location, local codes, and proper applications 
of: the 

National Fire Alarm and Signaling Code

 

(NFPA 72), ANSI A117.1; the appropriate model 
building code: BOCA, ICBO, or SBCCI; and the 
application guidelines of the Americans with Disabilities 
Act (ADA). 

IDNAC SLC Operation Advantage 

 

TrueAlert addressable appliances on IDNAC SLCs

 

provide separate visible (and audible) notification using a 
single two-wire circuit that also 

confirms connection to the 

individual notification appliance’s electronic circuit

. This 

operation increases circuit supervision integrity by providing 
supervision that extends beyond the appliance wiring 
connections. 

Reduced current allows efficient IDNAC SLC 
operation.

 With 

IDNAC SLCs

, a 

constant

 29 VRMS 

source voltage is maintained, even during battery standby, 
allowing strobes to operate at higher voltage with lower 
current and ensuring a consistent current draw and voltage 
drop margin under both primary power and secondary 
battery standby. Efficiencies include wiring distances up 
to 2 to 3 times farther than with conventional notification, 
or support for more appliances per IDNAC SLC, or use of 
smaller gauge wiring, or combinations of these benefits, 
all providing installation and maintenance savings with 
high assurance that appliances that operate during normal 
system testing will operate during worst case alarm 
conditions. 

 

TrueAlert Addressable Notification Appliances 

UL, ULC, CSFM Listed; FM Approved;

 

 Multi-Candela Visible Only (V/O)  

MEA (NYC) Acceptance*

 

Appliances (Strobes), Ceiling Mount

 

 

 

S4906-0004-3  5/2013

 

 

Содержание TrueAlert 4906-9202

Страница 1: ...nt of Buildings MEA35 93E Additional listings may be applicable contact your local Simplex product supplier for the latest status Listings and approvals under Simplex Time Recorder Co are the property of Tyco Safety Products Westminster Ceiling Mount Addressable V Os Description Multi Candela TrueAlert addressable strobes provide convenient installation to standard electrical boxes The strobe is i...

Страница 2: ...after the address is indicated by pulsing the appliance LED the strobe will briefly flash to indicate proper operation TrueStart Instrument Two TSIT The 2nd generation of the Simplex TrueStart Test Instrument adds testing of IDNAC SLC wiring and TrueAlert and TrueAlert ES appliances to its ability to test IDCs NACs and IDNet communications before connection to the control panel Please contact your...

Страница 3: ...e for Retrofit Applications Voltage Range 17 VRMS to 31 VRMS Special Application Candela Setting 15 cd 30 cd 75 cd 110 cd 17 VRMS Current Ratings use when connected to TrueAlert Addressable SLCs per above 76 mA 128 mA 242 mA 328 mA General Specifications see page 2 for dimensions Environmental 32 to 122 F 0 to 50 C 10 to 93 non condensing at 100 F 38 C Connections Terminal blocks for 18 AWG to 12 ...

Страница 4: ...aling Code are registered trademarks of the National Fire Protection Association NFPA Tyco Fire Protection Products Westminster MA 01441 0001 USA S4906 0004 3 5 2013 www simplexgrinnell com 2013 Tyco Fire Protection Products All rights reserved All specifications and other information shown were current as of document revision date and are subject to change without notice ...