6-2
Logging In and Out of the System
Introduction
The FACP system has four access levels. Level 1 is the lowest access level; level 4 is the highest
access level. Each display function may be programmed for any access level from the FACP
Programming tool. By default, access level 1 is adequate for typical front panel operations, such as
Alarm Acknowledge, Signal Silence and System Reset. To see the access levels from within the
FACP Programmer, select the "Panel" tab. The third item is named "Access Levels." Select this
tab to see a list of all display functions and the assigned access level.
Log-in at access level 4 causes a "Service Mode" trouble. This trouble requires a "warm-start" to
clear. To warm-start the panel, either press the reset switch (located on the edge of the CPU card)
for approximately 1 second or activate the front panel menu option.
Procedure
Follow these steps to log into the system at access level two, three, or four. The keypad used to
enter the passcode is located behind the interface panel access door.
1.
Obtain the passcode for the access level at which you want to operate.
2.
Press MENU on the entry keypad, located on the right side of the interface panel.
3.
Press the direction keys until the cursor highlights “Access.” Press ENTER or the “Select
Item” softkey.
4.
Scroll the cursor to the “Login” command, and press ENTER or the “Select item” softkey. The
following screen appears.
Figure 6-1. Login screen.
5.
Enter the passcode for the access level. The passcode can be up to 10 numbers in length. Press
the ENTER key on the Display/Action keypad or the “Enter” softkey when you have finished
entering the code. An asterisk is displayed for each digit of your passcode, as shown above.
Log Out Procedure
Failure to log out allows unauthorized personnel access to the various passcode protected functions.
If no keypad activity is detected for ten minutes, the system returns to Level 1 access.
Perform the following procedure to log out and return the operator access level to Level 1.
1.
Press the MENU key.
2.
Scroll to the “Access” command, and press ENTER or the “Select Icon” softkey.
3.
Scroll to “Log Out” and press ENTER. The panel is at access level 1.
4.
Press CLR/Exit to go back to the normal operation screen.
firealarmresources.com
Содержание InfoAlarm 4100ES
Страница 1: ...Operator s Manual Part InfoAlarm Product 4100U 4100ES 579 685 Rev B firealarmresources com ...
Страница 2: ...ii firealarmresources com ...
Страница 3: ...iii firealarmresources com ...
Страница 10: ...firealarmresources com ...
Страница 50: ...firealarmresources com ...
Страница 63: ...firealarmresources com ...
Страница 64: ...579 685 Rev B firealarmresources com ...