Atlas | Operation and Installation Manual
16
VII-D. Trouble Shooting
Error
Problem
Solution
Intake
Temp.
Failure
Intake screen blocked by debris
Ambient temperature too high
Clear intake screen, located
on bottom of unit.
Move load bank to cooler
location or wait to conduct
test on cooler day, if possible.
Exhausts
Temp.
Failure
Fan has stopped running
Exhaust space insufficient
The unit needs to be
serviced. Please call the
Simplex service department
at 800-637-8603 ext. 4.
Move the unit to an area that
allows for proper air
circulation. See “Load Bank
Placement” on page 8 for
more information.
Fan failure
Fan not blowing air into element
chamber
Fan blades not turning
Clear intake screen, located
on bottom of unit.
Make sure nothing has
jammed the fan blades.
Over
Voltage
Load bank connected to too-high
voltage source
Connect load bank to
appropriate voltage source.
Maintenance/Troubleshooting -