Electrical Ratings 

Typical Operating Voltage Range 

23 VRMS to 31 VRMS, Special Application (see below for 17 VRMS rating) 

Supervisory Requirements 

1 unit load 

SLC Loading 

Maximum of 63 addresses per SLC, 75 unit loads  

Candela Setting 

15 cd 

30 cd 

75 cd 

110 cd 

135 cd 

185 cd 

23 VRMS

 Current Ratings, for typical design of 

IDNAC Addressable SLCs (6 VRMS drop) 

47 mA 

57 mA 

100 mA 

132 mA 

160 mA 

208 mA 

General Specifications 

Temperature Range 

32

 to 122

 F (0

 to 50

 C) 

Humidity Range 

10% to 93%, non-condensing @ 104° F (40° C) 

IDNAC SLC Wiring Specifications

 

(refer to control panel installation instructions 
for more information) 

UTP, unshielded twisted pair recommended 
Maximum wire length allowed with “T-Taps” for Class B wiring per SLC = 10,000 ft 
(3048 m) 
Maximum wire length to any appliance = 4000 ft (1219 m) 
Maximum wiring resistance between compatible appliances = 26 

 

Connections 

Terminal blocks on mounting plate for 18 AWG to 12 AWG (0.82 mm

2

 to 

3.31 mm

2

); two wires per terminal for in/out wiring 

Installation Instructions 

579-1031 

Notes: 

Refer to compatibility table above for fire alarm control panel and power supply operation type. 

TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National Fire Alarm Code 
are trademarks of the National Fire Protection Association (NFPA).

 

 

 

Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA

 

S49VO-0001-3  8/2014

 

 

www.simplex-fire.com

 

© 2014 Tyco Fire Protection Products. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice. 

 

Compatible Controller 

Data Sheet 

Reference 

Controller Output 

Available Strobe 

Intensity 

Appliance Voltage 

Minimum 

4100ES or 4100U with 
TrueAlert Power Supply 

S4100-0031 

TrueAlert  

Addressable SLC 

15, 30, 75, and 110 cd 

17 VRMS 

4009 TPS, Remote 
TrueAlert Power Supply 

S4100-0037 

TrueAlert Addressable 
Controller (4009T) 

S4009-0003 

Electrical Ratings Reference for Retrofit Applications 

Voltage Range  17 VRMS to 31 VRMS, Special Application 

Candela Setting 

15 cd 

30 cd 

75 cd 

110 cd 

17 VRMS

 Current Ratings, use when 

connected to TrueAlert Addressable SLCs per 
above 

62 mA 

75 mA 

133 mA 

178 mA 

Compatible Controller and additional 
TrueAlert ES Appliances 

Data Sheet 
Reference 

Controller 

Output 

IDNAC SLC  

Output Voltage  

Appliance Voltage 

Design Reference 

4100ES with EPS+ or EPS Power Supply 

S4100-0100 

IDNAC SLC 

29 VRMS 

(regulated) 

23 VRMS 

(with 6 VRMS drop) 

4009 IDNAC Repeater 

S4009-0004 

TrueAlert ES Audible Only (Horns) 

S49AO-0001 

TrueAlert ES Audible/Visible 

S49AV-0001 

TrueAlert ES Weatherproof 
Appliances 

UL Listed  S49WP-0001 

ULC Listed  S49WP-0002 

 TrueAlert ES Strobe Specifications 

 TrueAlert ES Strobe LEGACY Compatibility Reference 

 TrueAlert ES Appliance and IDNAC SLC Controller Compatibility Reference 