Setting the Ceiling-Mount A/V Address

 

 

Each TrueAlert notification appliance has a unique address.  Each appliance’s address is set via an eight-position DIP 
switch, as shown in Table 2 (see Figure 3 for the general DIP switch location).  DIP switch position 1 is the least 
significant bit (LSB) and position 8 is the most significant bit (MSB).   

 

Note: 

DIP Switches 1 through 6 are used to set the possible 63 address codes. DIP Switches 7 and 8 are not used and 
are set to “OFF.” 

 

Use a small screwdriver or pen to set the switches, and then record the address.  This information provides an aid in 
troubleshooting the system. 

 

Table 2.  TrueAlert Ceiling-Mount A/V Units – DIP Switch Address Chart 

0000

1000

0100

1100

0000

0

16

32

48

1000

1

17

33

49

0100

2

18

34

50

1100

3

19

35

51

0010

4

20

36

52

1010

5

21

37

53

0110

6

22

38

54

1110

7

23

39

55

0001

8

24

40

56

1001

9

25

41

57

0101

10

26

42

58

1101

11

27

43

59

0011

12

28

44

60

1011

13

29

45

61

0111

14

30

46

62

15

31

47

63

LSB

MSB

1

2

3

4

5

6

7

8

1111

DIP SWITCHES 5 AND 6

DIP

SWITCHES

1 THRU 4

RESERVED FOR

FUTURE USE

NOT USED

ON

OFF

1 = ON

0 = OFF

DIP SWITCH SHOWN IS

SET AT ADDRESS 7.

 

 

Ceiling-Mount A/V Magnetic Test  

 

Note:

  The TrueAlert Addressable Controller must be configured to support the 

Ceiling-Mount A/V diagnostic testing. 

 
Position magnet tester 553-810 to the bottom right side of the A/V cover near 
the LED indicator (see Figure 4).  Hold the magnet tester in place for a 
minimum of two seconds or until the LED begins flashing. 
 
In response to the magnetic test, the A/V LED emits one long flash denoting the 
test acknowledge signal, and then another long flash denoting the first digit 
(always zero) of the appliance address.  The LED then flashes one to six times to 
denote the second digit of the address, pauses, and then flashes one to nine times 
to indicate the third digit of the address.  One long flash always indicates a zero.  
After the A/V LED flashes its address, the A/V goes into alarm (real appliance 
test) or the LED illuminates (silent appliance test) for 2 to 3 seconds. 

 

Important:

   Refer to the TrueAlert Addressable Controller Installation 

Guide(574-762) for detailed information on appliance 
diagnostic testing. 

 

 

Figure 4.  Appliance Magnet Test 

MAGNET 

TESTER 

LOCATION 

A/V LED 

firealarmresources.com

Содержание 4903

Страница 1: ...e TrueAlert Ceiling Mount A V Operation The 4903 TrueAlert Audible Visible A V unit see Figure 1 is a ceiling mount notification appliance that provides an audible and or visible warning indication of an alarm condition when activated from a TrueAlert compatible control panel of a UL listed Simplex Fire Alarm System When the notification appliance emits sound and or light it indicates the possibil...

Страница 2: ... Maximum 30 ohms wire resistance between appliances Refer to Field Wiring Diagrams of the driving TrueAlert compatible Fire Alarm Control Panel for further instructions 2 Notification appliances are rated per individual nameplate label 3 Maintain correct polarity on terminal connections Do not loop wires under terminals 4 All TrueAlert SLC wiring connections are supervised and power limited 5 Thes...

Страница 3: ...unted Ensure correct orientation of the box in relation to the location of the mounting screws and the A V s position 2 For installation in a concrete or plaster ceiling flush mount the box with a inch recess maximum 3 For installation in a suspended ceiling use a suitable tile bridge that rests on tile to support the box 4 Address Switch SW1 is accessible with the Ceiling Mount A V removed Figure...

Страница 4: ... 1 THRU 4 RESERVED FOR FUTURE USE NOT USED ON OFF 1 ON 0 OFF DIP SWITCH SHOWN IS SET AT ADDRESS 7 Ceiling Mount A V Magnetic Test Note The TrueAlert Addressable Controller must be configured to support the Ceiling Mount A V diagnostic testing Position magnet tester 553 810 to the bottom right side of the A V cover near the LED indicator see Figure 4 Hold the magnet tester in place for a minimum of...

Страница 5: ... volume settings Table 4 TrueAlert Ceiling Mount A V Units Sound Pressure Level Measurements Sound Pressure Level Measurement dBA Voltage Vrms Horn Mode See Note 1 Reverberant Room at Ten Feet Per UL464 See Note 2 Steady 84 6 Coded 80 6 Steady 86 3 Coded 82 4 Steady 88 4 High Volume Setting via Addressable Controller See Note 3 Coded 84 5 Steady 79 1 Coded 75 5 Steady 81 5 Coded 77 2 Steady 84 3 L...

Страница 6: ...ese occupants cannot hear and or see the effect of the notification appliances within the protected area s you must increase the intensity of the sound light output or add additional notification appliances so that the occupants can hear an or see the effect of the notification appliances when activated Refer to National Fire Protection Association NFPA National Fire Alarm Code 72 Chapter 4 Notifi...

Отзывы: