Features
Panel mounted modules provides fire alarm
system status using the ASHRAE BACnet
building automation communication protocol
BACnet (Building Automation Control Network)
protocol reference:
Communications are via BACnet IP (internet protocol)
Reference: ANSI/ASHRAE Standard 135
Connections:
To fire alarm system via RS-232 port B, configured
for Computer Port Protocol (see page 3 for model
number reference per panel)
Output port provides Ethernet LAN (local area
network) connection
BACpac Ethernet Module is pre-programmed:
Module is pre-programmed with digital pseudo points
linked to BACnet objects
Up to 1000 status changes (monitor point status) can
be recognized from the fire alarm control panel
Compatible Simplex
®
fire alarm control panels:
4100ES and 4100U Series fire alarm control panels
and Network Display Units (NDU)
4010ES Series fire alarm control panels
Installed legacy Models 4100/4100+ and 4120 Series
fire alarm control panels and NDU (software revision
updating may be required
Listings reference:
UL listed to Standard 864
ULC listed to Standard S527
Description
The BACpac Ethernet module provides a supplementary
communications interface that converts computer terminal
information from a compatible Simplex fire alarm control
panel into the building automation protocol of BACnet.
With this module, status information from the fire alarm
control panel can be provided to other components of the
building automation network with the detail and
information format required.
Providing this information allows other systems to
properly respond to fire alarm system activity in addition
to the primary fire alarm response that is under the control
of the fire alarm control panel.
ALARM
FIRE
PULL DOWN
ALARM
FIRE
PULL DOWN
LAN Connected BACnet System Controllers
Facility LAN
System
Workstation
Fire Alarm
Network
Fire alarm
initiating devices
Simplex Fire Alarm
Control Panel
Fire Alarm System
ALARM
ALARM
4100-6069 BACpac
Ethernet Module
Facility LAN
Fire Control
FI RE A LARM
CONTROL
DIS CONNECT
P OW ER B E FORE
S ERVI CI NG
CAUTION
** SY ST EM IS NORMAL * *
1 2: 02: 15p m Mo n 8- Ma r-99
SU P
V
AC K
SYS TEM
SUP ERVI SO R
Y
AL ARM
A CK
F IR E
AL ARM
TR OU BLE
ACK
SYST EM
TROU BL
E
ALAR M
SI L
E N CE
ALAR M
SIL ENC ED
SYS TEM
R ES E
T
A C
P OW ER
Typical Building Automation LAN with
Simplex Fire Alarm Control Panel and BACpac Portal
(shown with 4100ES panel for reference)
This document is a summary of the flexibility available
with BACnet communications. Please contact your local
Simplex product supplier for further information
concerning your specific application.
*
This product has been approved by the California State Fire Marshal (CSFM) pursuant to
Section 13144.1 of the California Health and Safety Code. See CSFM Listing
7165-0026:0251 (4100 Series) or 7165-0026:0369 (4010ES) for allowable values and/or
conditions concerning material presented in this document. It is subject to re-examination,
revision, and possible cancellation. This product was not approved by FM, or accepted by
MEA (NYC) as of document revision date. Additional listings may be applicable; contact
your local Simplex product supplier for the latest status. Listings and approvals under
Simplex Time Recorder Co. are the property of Tyco Fire Protection Products.
Fire Control Panels
UL, ULC, CSFM Listed*
BACpac
Ethernet Portal Modules
Model 4100-6069 and 4010-9915
S4100-0051-3 9/2012