![Simex SUR-94 Скачать руководство пользователя страница 6](http://html1.mh-extra.com/html/simex/sur-94/sur-94_user-manual_1275403006.webp)
User manual - METER SUR-94
Active current output
(optional, for two relays or two
OC-type output version only)
range max. 0 ÷ 24 mA
Load resistance max.
700
Ω
Passive isolated current output
(optional, for two relays or two
OC-type output version only)
range max. 2.8 ÷ 24 mA
Supply voltage
Us = 9.5 ÷ 36V
Load resistance max.
(Us – 9.5V) / 24mA [k
Ω
]
Active voltage output
(optional, for two relays or two
OC-type output version only)
range max. 0 ÷ 11V
Load resistance min.
2000
Ω
Temperature stability
50 ppm / °C
Display range
-999 ÷ 9999, plus decimal point
Communication interface
RS-485, 8N1 and 8N2, Modbus RTU,
not separated
Baud rate
1200 bit/s ÷ 115200 bit/s
Display
(depending on version)
LED, 4 digit, 20mm height, red or
LED, 4 digit, 20mm height, green
Data memory
non-volatile memory, EEPROM type
Front panel protection
IP 65
optional version with panel cut-out sealing available
Terminals protection
IP 20
Housing type
Housing material
Housing dimensions
Mounting hole
Assembly depth
Panel thickness
panel
NORYL - GFN2S E1
96 x 48 x 100 mm
90.5 x 43 mm
102 mm
max. 5 mm
Operating temperature
(depending on version)
0°C to +50°C
or -20°C to +50°C
Storage temperature
(depending on version)
-10°C to +70°C
or -20°C to +70°C
6
Содержание SUR-94
Страница 58: ...User manual METER SUR 94 58...
Страница 59: ...User manual METER SUR 94 59...