User manual - METER SRT-L70
Temperature stability
50 ppm / °C
Outputs
relay:
sensor power supply:
3 (2 NO and 1 NONC), 8A/250V AC (cos
ϕ
= 1)
24V +5%, -10% / max. 100 mA, stabilized,
not separated from measurement inputs
Communication interface
RS 485, 8N1 and 8N2, Modbus RTU,
not separated
Baud rate
1200 bit/s ÷ 115200 bit/s
Display
LED, 4 digit, 13mm height, red
Data memory
non-volatile memory, EEPROM type
Protection level
IP 20 (housing and connection clips)
Housing type
Housing material
Housing dimensions
DIN rail mounted (35 mm rail)
NORYL UL 94 V-0
72 x 91 x 59 mm
Operating temperature
(depending on version)
0°C to +50°C
or -20°C to +50°C
Storage temperature
(depending on version)
-10°C to +70°C
or -20°C to +70°C
Humidity
Altitude
5 to 90% no condensation
up to 2000 meters above sea level
Screws tightening max. torque
0,5 Nm
Max. connection leads diameter
2,5 mm
2
Safety requirements
according to: PN-EN 61010-1
installation category: II
pollution degree: 2
voltage in relation to ground: 300V AC
insulation resistance
: >20M
Ω
insulation strength between power supply and
input/output terminal: 1min. @ 2300V
insulation strength between relays terminal:
1min. @ 1350V
EMC
according to: PN-EN 61326-1
This is a class A unit. In a residential or a similar area it can cause radio
frequency interference. In such cases the user can be requested to use
appropriate preventive measures.
5
!