8
SPT-85
Instrukcja obs³ugi przetwornika temperatury / Operation manual of temperature transmitter
10. TECHNICAL DATA
Input signal
: Pt 100 (w=1.385), 3-wire
-100 ... +850°C
Pt 1000 (w=1.385), 3-wire
-100 ... +600°C
PTC, 3-wire
-50 ... +150°C (1k
W
, 2k
W
at 25 °C)
minimum range width: 50°C
thermocouple „T” (Cu-CuNi)
-40 ... +400°C
thermocouple „J” (Fe-CuNi)
-20 ... +1000°C
thermocouple „K” (NiCr-Ni)
-20 ... +1300°C
thermocouple „R” (PtRh13-Pt)
0 ... +1700°C
thermocouple „S” (PtRh10-Pt)
0 ... +1700°C
thermocouple „B” (PtRh30-PtRh6)
200 ... +1800°C
minimum range width: 100°C
linear voltage
0-100 mV DC
custom linear (AUX)
0-10 V DC (
o
ption
:
0-20 mA, 4-20 mA)
Power supply
: 8-32 VDC ±10%
Maximum line load
: 75
0 Ù
at
24 VDC
/ 20 mA
Output
: 2-wire, 4-20 mA, programmable
Resolution
: 4 µA (12-bit)
Accuracy
: ±
0
,
1%
Measurement error
: 0,3 % from span
Temperature drift
: ± 0,01% from span for 1°C
Digital filter
: programmable
Digital peak filter
:
programmable
Sensor break reaction
: < 3,8 or > 20,2 mA, programmable
Communication interface
: RS-232
Programmability
:
with
configuration
software ”TraCon”
(option)
Operating temperature
: -20 to 85°C
Operating humidity
:
0 to 9
0
% RH, non-condensing
Protection class
: IP 20
Dimensions
:
Ø43 x 23 mm
(G head mounting); 90 x 18 x 58 mm (DIN-rail mounting, L)
Weight
: 40 g (head mounting); 60 g (DIN-rail mounting)
EMC
:
EN 50081-1, EN 50082-2,
89/336/EEC
11. DIMENSIONS
1
2
3
4
5
6
23
O
44
Fig. 11.1.: H
ransmitter’s dimensions
ead mounting t