User manual - MODULE SOC-8 

At this moment MASTER controller should find new device and readdress it (to address 

other than 0xFF and 0xFE). After remote readdressing green LED indicator starts to flashes 

again.

Simultaneously with change of device address, baud rate is changed to 9600 bit/s. 

Required transmission speed (1200 bit/s. to 115200 bit/s.) can be set by write to register 22h. 

After change of transmission speed the device sends the answer with new  baud rate. While 

installation of the new network it is recommended to readdress all devices using   baud rate 

9600 bit/s, and next change speed of all devices simultaneously, using  BROADCAST query 

(with address 00h).

5.1. 

 

     EXAMPLES OF OUTPUT CONT

 

 ROLLING

 

 

1. No control of communication lost

Content of registers :

 0Bh = 0; 0Ch = 0; 0Dh = FF00h;

Operation:

 Device do not controls delays between successive writings. After power on 

outputs are set to state FFh. 

2. Control without PRE-alarm

Content of registers :

 0Bh = 0; 0Ch = 60; 0Dh = FF00h;

Operation

: After 60 seconds since last write to any of output registers  the device goes to 

FINAL state, and sets its outputs to  FFh.  The device stays in this state to  the next write 

to any of output registers. After power on outputs are set to state FFh. 

3. Control with PRE-alarm

Content of registers :

 0Bh = 120; 0Ch = 60; 0Dh = FF00h;

Operation

: After 120 seconds since last write to any of output registers the device goes to 

PRE-alarm state, and sets its outputs to 00h. After next 60 seconds since last write to 

any of output registers the device goes to FINAL state, and sets its outputs to  FFh.. The 

device stays  in this state to  the next write to any of output registers. After power on 

outputs are set to state FFh. 

4. Control with PRE-alarm, without FINAL-state

Content of registers :

 0Bh = 120; 0Ch = 0; 0Dh = FF00h;

Operation: 

After 120 seconds since last write to any of output registers the device goes to 

PRE-alarm state, and sets its outputs to 00h. The device stays in this state to the next 

write to any of output registers or to power supply off. After power on outputs are set to 

state FFh. 

9

Содержание SOC-8

Страница 1: ...SOC 8 Firmware v 2 0 or higher Input type voltage OC Dedicated for DAQ systems Read the user s manual carefully before starting to use the unit or software Producer reserves the right to implement ch...

Страница 2: ...ERRORS DESCRIPTION 11 6 3 EXAMPLES OF QUERY ANSWER FRAMES 11 Explanation of symbols used in the manual This symbol denotes especially important guidelines concerning the installation and operation of...

Страница 3: ...ot attempt to disassemble repair or modify the unit yourself The unit has no user serviceable parts Defective units must be disconnected and submitted for repairs at an authorized service centre The u...

Страница 4: ...ng max torque 0 5 Nm Max connection leads diameter 2 5 mm2 EMC according to PN EN 61326 1 This is a class A unit In housing or a similar area it can cause radio frequency interference In such cases th...

Страница 5: ...he thread In the case of the unit being fitted with separable clamps they should be inserted into appropriate connectors in the unit even if they are not used for any connections Unused clamps marked...

Страница 6: ...f the outputs GND and Vpp must be connected to the module these signals are required for proper operation of the module It is recommended to separate output signals power and GND from power supply of...

Страница 7: ...ive load connection Figure 4 5 Recommended method of inductive load connection 7 power supply 8 x driver P RS 485 power supply 0V outputs RS 485 interface optoisolation 24V 24V GND OUT1 OUT8 OUT8 OUT6...

Страница 8: ...for controlling the state of the outputs while lost of communication with HOST device The content of 0Dh register decides about the state of the outputs after communication lost Its lower byte is a PR...

Страница 9: ...tent of registers 0Bh 0 0Ch 60 0Dh FF00h Operation After 60 seconds since last write to any of output registers the device goes to FINAL state and sets its outputs to FFh The device stays in this stat...

Страница 10: ...off 09h Yes 0 00FFh The state of all outputs bits are ascribed to outputs Bit 0 corresponds to OUT1 bit 1 to OUT2 and so on 0Bh Yes 0 FFFFh PRE alarm delay expressed in seconds 0 PRE alarm is off 0Ch...

Страница 11: ...ion ADDR Device address on modbus network FUNC Function code REG H L Starting address address of first register to read write Hi and Lo byte COUNT H L No of registers to read write Hi and Lo byte BYTE...

Страница 12: ...same as the message ADDR FUNC REG H L DATA H L CRC L H 01 06 00 01 00 01 19 CA 4 Simultaneous change of all outputs state ADDR FUNC REG H L COUNT H L CRC L H 01 03 00 09 00 01 54 08 The answer ADDR F...

Страница 13: ...User manual MODULE SOC 8 13...

Страница 14: ...User manual MODULE SOC 8 14...

Страница 15: ...User manual MODULE SOC 8 15...

Страница 16: ...SIMEX Sp z o o ul Wielopole 7 80 556 Gda sk Poland tel 48 58 762 07 77 fax 48 58 762 07 70 http www simex pl e mail info simex pl...

Отзывы: