2. Change of the device address from 1 to 2 (write to reg. 20h)
ADDR
FUNC
REG H,L
DATA H,L
CRC L,H
01
06
00
20
00
02
09
C1
DATA H - 0
DATA L - new device address (2)
The answer (the same as the message):
ADDR
FUNC
REG H,L
DATA H,L
CRC L,H
01
06
00
20
00
02
09
C1
3. Change of baud rate of all devices connected to the net (BROADCAST message).
ADDR
FUNC
REG H,L
COUNT H,L
CRC L,H
00
06
00
22
00
04
29
D2
DATA H - 0
DATA L - 4, new baud rate 19200 baud
Device do not reply to BROADCAST-type messages.
4. Read of the displayed value (higher word):
ADDR
FUNC
REG H,L
COUNT H,L
CRC L,H
01
03
00
01
00
01
D5
CA
Response, while normal operation (no errors):
ADDR
FUNC
BYTE C
DATA H,L
CRC L,H
01
03
02
00
00
B8
4C
DATA H, L - 0000h = 0, higher word of displayed value = 00
5. Read of the displayed value (high and low word),
ADDR
FUNC
REG H,L
COUNT H,L
CRC L,H
01
03
00
01
00
02
95
CB
43
i