User manual for  digital indicator with U/I input SWE-73-A

“Lo C”
“Hi C”

These parameters describe the values displayed for minimum and maximum input 
current. For example, if input type is set to 4-20 mA 

“Lo C”

 parameter defines the 

value displayed when input current is equal 4 mA, and   

“Hi C”

  parameter defines 

the   value   displayed   for   20   mA   of   input   current.   Available   range   for   these 
parameters:  -999 ÷ 9999. Negative values can be set by entering  

'-'

 sign on the first 

position  (by use of 

[^]

,

 [v]

 buttons).

If   user   defined   characteristic   is   selected  

(parameter  

“CHAr”  

=

  ”USEr”

)   the 

parameters „

Lo C

” and „

Hi C

” are not available for modification, due to their values 

are calculated from defined characteristic.

“AddP” 

- this menu allow user to add single point to the user defined characteristic.
After selection of this option device waits for „

X

” and „

Y

” coordinates of new point. 

Modification of the coordinates is done accordingly to numerical parameters edition. 
Coordinate „

X

”   defines the percentage ratio of   input current to selected current 

range. The „

X

”   range:   -99,9 ÷ 199,9. Coordinate „

Y

” defines displayed value for 

particular „

X

” value. The „

Y

” value can be changed in range: -999 ÷ 9999, decimal 

point position depend on 

„Pnt”

 parameter (menu 

”inPt ”

).

User can not enter two points with the same value of „

X

” coordinate. If user trays 

to do it,  

”Err”

  warning is displayed. To modify any defined point use  

”EdtP” 

option.

To   distinguish   „

X

”   and   „

Y

”   coordinates,   if   „

X

”   coordinate   is   displayed   an 

additional decimal point on utmost right position is displayed.

If user defined characteristic is selected, and if number of defined points is lower 
than 2 then warning ”

Errc

” is displayed in measurement mode.

“dELP” 

-   this   option   allows   user   to   delete   any   of   the   points   of   the   user   defined 

characteristic.   After   selection   current   number   of   points   of   the   user   defined 

characteristic   is   displayed   for  about   approx.   1.5   sec.   After  that   device   waits   for 
selection of point being deleted (by 

[^]

[v]

 buttons). The short pressing of 

[ENTER] 

button causes by switching between 

X

 and 

Y

 value of the displayed point.  The long 

press   (press   and   hold   at   least   2   sec)   of  

[ENTER]

  button   causes   by  displaying 

„dEL?” 

ask. If 

[ENTER]

 button is pressed again, current point is deleted and new 

updated number of points of the user defined characteristic is displayed.

“EdtP” 

-   this   option   allows   user   to   modify   of   particular   point   of   the   user   defined 

characteristic.   After   selection   current   number   of   points   of   the   user   defined 

characteristic   is   displayed   for  about   approx.   1.5   sec.   After   that   device   waits   for 
selection of point being edited (by 

[^]

[v]

 buttons). The short  pressing of 

[ENTER] 

button causes by switching between 

X

 and 

Y

 value of the displayed point.  The long 

press (press and hold at least 2 sec) of 

[ENTER]

 button causes by entering to edit 

the   selected   coordinate   of   the   point.   Modification   of   the   coordinates   is   done 

accordingly to numerical parameters edition. 

“AddP”

,

  ”dELP”  

and  

“EdtP”

  options   are   available   only   if   the   user   defined 

characteristic is used (it means when parameter 

“CHAr” 

=

 ”USEr”

).

“Lo r”

,

 ”Hi r”

- these parameters define the expansion of nominal range in percent. They 

18

i

i

i

Содержание SIMPACT SWE-73-A

Страница 1: ...indicator with U I input family type SWE 73 A firmware version 5 14 or higher Read the user s manual carefully before starting to use the unit Producer reserves the right to implement changes without...

Страница 2: ...eters slide change mode 15 7 2 3 Switch parameters LIST type 16 7 3 MENU DESCRIPTION 17 7 3 1 inPt menu 17 7 3 2 bri parameter 19 7 3 3 HOLd menu 20 7 3 4 Scod parameter 20 7 3 5 rS menu 20 7 3 6 Edit...

Страница 3: ...to the application Incorrect configuration can cause defective operation which can lead to unit damage or an accident If in the case of a defect of unit operation there is a risk of a serious threat t...

Страница 4: ...re root and user defined max 20 points length Result is showed on 4 digit LED display Displayed values range can be selected by user from 999 to 9999 plus decimal point Device SWE 73 A is equipped wit...

Страница 5: ...embly depth 67 x 32 5 mm for 24V DC version min 78 mm for 230V AC version min 95 mm Panel thickness max 5 mm Operating temperature depending on version 0 C to 50 C or 20 C to 50 C Storage temperature...

Страница 6: ...g check for transportation damage Any transportation damage must be immediately reported to the carrier Also write down the unit serial number on the housing and report the damage to the manufacturer...

Страница 7: ...SWE 73 A Figure 4 1 Mounting hole dimensions Figure 4 2 Installing of brackets and dimensions of connectors Figure 4 3 Minimum distances when assembly of a number of units 7 91 mm 57 mm 66 5 mm max 5...

Страница 8: ...ration Over tightening can lead to damaging the connections inside the units and breaking the thread In the case of the unit being fitted with separable clamps they should be inserted into appropriate...

Страница 9: ...connection between the filter and the unit should be as short as possible and the metal housing of the filter must be connected to the earthing with largest possible surface The cables connected to t...

Страница 10: ...re 4 6 Connection of power supply a for 230V AC version b for 24V DC version Figure 4 7 Connection of 2 wire current converters Figure 4 8 Connection of 3 wire current converters 10 FUSE 230V AC L N L...

Страница 11: ...s cause faster ageing of the internal components and shorten the fault free time of unit operation In cases where the unit gets dirty do not clean with solvents For cleaning use warm water with small...

Страница 12: ...g edited Symbol used in the manual v Functions Change of the present menu Modification of the parameter value Change of the display mode 6 PRINCIPLE OF OPERATION After turning the power supply on devi...

Страница 13: ...e 999 9999 the warning Ov is displayed rather than the calculated result Input type range of displaying values characteristic of conversion decimal point position and measure filtering ratio are user...

Страница 14: ...cess of peaks detection 7 DEVICE PROGRAMMING The device menu allow user to set all parameters connected to operation of measurement input control modes critical situations behaviour communication via...

Страница 15: ...he ENTER button causes change of the position digit Press ENTER at least 2 seconds to accept the changes after that question SEt is displayed and user must to confirm or cancel the changes To conform...

Страница 16: ...of made changes and returning to menu Functions of buttons when editing numeric and switching parameters While editing numeric parameter change of current flashing digit slide change of value acceler...

Страница 17: ...efined characteristic points and parameter Pnt CHAr this option presets type of the conversion characteristic and can be set to Lin linear Sqr square Sqrt square root When one of those characteristics...

Страница 18: ...itional decimal point on utmost right position is displayed If user defined characteristic is selected and if number of defined points is lower than 2 then warning Errc is displayed in measurement mod...

Страница 19: ...on Imin 4 mA 4 mA Lo r The Lo r value can be set from 0 to 99 9 Parameter Hi r determines the upper border of the permissible range accordingly to the expression for all modes For example if input is...

Страница 20: ...is set at value 0000 user password is turned off If the user do not remember his password the access to the menu is possible by the one use password To get this password please contact with Marketing...

Страница 21: ...depends on selected baud rate In the most cases parameter rESP should be set to Std no additional delay Unfortunately for some third party RS converters rESP should be adjusted experimentally Table 7...

Страница 22: ...rESP modE PEA timE Hdis Parameter edition SEt 4 digit special password entering 0 _ _ _ Default settings restoring Scod MENU ESC ENTER MENU ESC MENU ESC MENU ESC MENU ESC ENTER MENU ESC MENU ESC MENU...

Страница 23: ...input range 0 mA for 0 20mA range and 4mA for 4 20mA range must be subtracted from measured value Next received result must be divided by the width of the input range it means 20mA for 0 20mA range an...

Страница 24: ...acteristic The normalized result is squared and further conversion is done as for linear characteristic Conversion is made accordingly with the expression W I n 2 Hi C Lo C Lo C where W means the disp...

Страница 25: ...acteristic from figure below and In 0 65 the segment between points X 50 0 and X 70 0 will be chosen Let s mark those points as PL point low i PH point high in this example PL 50 0 and PH 70 0 and the...

Страница 26: ...mA then 10 mA 4 mA 6 mA and this result should be divided by the width of input range 16 mA Finally the normalized result In 6 16 0 375 In case when input current exceeds nominal measurement range cal...

Страница 27: ...on page 24 for linear characteristic 0 375 2 1200 300 211 and next the Lo C value is added to the result so the displayed value W 211 300 89 b Iin 2 5 mA and In 0 0938 W 287 c Iin 20 5 mA and In 1 03...

Страница 28: ...nd stored in the device memory a Iin 10 mA and In 0 375 The segment defined by X6 30 0 and X7 40 0 for this In will be selected Accordingly to expressions given for user defined characteristic see pag...

Страница 29: ...urrent measurement 0h data valid A0h top border of the measurement range is exceeded 60h bottom border of the measurement range is exceeded 03h Yes 0 3 Pnt parameter in InPt menu decimal point positio...

Страница 30: ...ressed in 0 1 71h5 Yes 999 9999 The value of Y coordinate of point no 1 of the user defined characteristic no decimal point included 72h5 95h5 Further pairs of X Y coordinates of points no 2 19 of the...

Страница 31: ...ingle register 10 3 EXAMPLES OF QUERY ANSWER FRAMES Examples apply for device with address 1 All values are represent hexadecimal Field description ADDR Device address on modbus network FUNC Function...

Страница 32: ...1 03 02 20 F2 20 01 DATA identification code 20F2h 3 Change of the device address from 1 to 2 write to reg 20h ADDR FUNC REG H L DATA H L CRC L H 01 06 00 20 00 02 09 C1 DATA H 0 DATA L new device add...

Страница 33: ...1 00 03 54 0B COUNT L the count of being read registers max 16 The answer ADDR FUNC BYTE C DATA H1 L1 DATA H2 L2 DATA H3 L3 CRC L H 01 03 06 00 0A 00 00 00 01 78 B4 DATA H1 L1 reg 01h 10 displayed val...

Страница 34: ...the bottom of the nominal input range 5 0 18 Hi r Extension of the top of the nominal input range 5 0 18 Display parameters bri Display brightness bri6 19 Configuration of peaks detection function HOL...

Страница 35: ...User manual for digital indicator with U I input SWE 73 A 35...

Страница 36: ...SIMEX SIMEX Sp z o o ul Wielopole 7 PL 80 556 Gda sk Poland tel 48 58 762 07 77 fax 48 58 762 07 70 http www simex com pl e mail info simex com pl...

Отзывы: