78
3.3
ACCESS TO
INSTALLER’S
PARAMETERS
For.access.to.the.installer’s.parameters,.
press. simultaneously. the. keys
.
5
3
1
2
4
.
and
.
5
3
1
2
4
.
or.2.seconds.(3.fig..12).
..
For. example,. the. parameter. PAR. 23. is.
visualised. on. the. display. of. the. control.
panel.in.the.following.way:
The. parameters. scroll. forwards. and.
backwards.with.the.key
.
5
3
1
2
4
.
and
.
5
3
1
2
4
and.
the. default. parameters. can. be. changed.
with.the.keys
.
5
3
1
2
4
.
and
.
5
3
1
2
4
.
.
The.standard.visualisation.returns.auto-
matically. after. 60. seconds,. or. by. pres-
sing. one. of. the. control. keys. (2. fig.. 12).
excluded.the.key.RESET.
3.3.1 Replacing the board or
RESETTING parameters
If. the. electronic. board. is. replaced. or.
reset,.it.is.necessary.to.configure.PAR.1.
and. PAR. 2. by. associating. the. following.
values.to.each.type.of.boiler.to.be.able.to.
restart.the.boiler:.
1.
.Visualizzazione.temperatura
.....esterna.solo.con.sonda.esterna.collegata
2...Visualizzazione.temperatura.sonda
.....riscaldamento.(SM)
3...Visualizzazione.temperatura.sonda
.....sanitario.(SS).solo.per.caldaie.istantanee
4. .Visualizzazione.temperatura.sonda
.....ausiliaria.o.sonda.bollitore.(SB)
6..Visualizzazione.temperatura
.....riscaldamento.riferita.al.primo.circuito
7..Visualizzazione.temperatura
.....riscaldamento.riferita.al.secondo.circuito
13...Visualizzazione.codice.errore
.......penultima.anomalia
14...Visualizzazione.numero.totale
.......delle.anomalie
9...Visualizzazione.numero.giri.ventilatore.in.rpm.x.100.(es..4.800.e.1.850.rpm)
10...Visualizzazione.ore.di.funzionamento.del.bruciatore.in.h.x.100.(es..14.000.e.10)
11...Visualizzazione.numero.di.accensioni.del.bruciatore.x.1.000.(es..97.000.e.500)
12...Visualizzazione.codice.errore
.......ultima.anomalia
15...Contatore.accessi.parametri
.......installatore.(es..140.accessi)
5...Visualizzazione.temperatura
.....sonda.fumi
8...Visualizzazione.corrente
.....di.ionizzazione.in.µA
16...Contatore.accessi.parametri
.......OEM.(es..48.accessi)
PARAMETERS INSTALLER
FAST CONFIGURATION
PAR. DESCRIPTION...
RANGE.
UNIT.OF.
INC/DEC.. DEFAULT
.
.
.
MEASUREMENT. UNIT.
SETTING
.1
.
Combustion.configuration
.
--.=.ND.
=.
=.
“-.-”
.
.
1.....63
.
.
.
.2
.
Hydraulic.configuration
.
--.=.ND.
=.
=.
“-.-”
.
.
1.....14
.3.
Timetable.2.programmer.
1.=.DHW.+.Recirc..pump.
=.
=.
1
..
.
2.=.DHW.
.
.
3.=.Recirculation.pump
.4.
Pressure.transducer.disabler.
0.=.Disabled.
=.
=.
1
.
.
1.=.Enabled.0-4.BAR
.
.
2.=.Enabled.0-6.BAR
.
.
3.=.Enabled.0-4.BAR.(NO.ALL.09)
.
.
4.=.Enabled.0-6.BAR.(NO.ALL.09)
.5.
Assignment.of.auxiliary.relay.AUX.. 1.=.Remote.supply.
=.
=.
1
.
.
2.=.Recirculation.pump
.
.
3.=.Automatic.load.
.
.
4.=.Remote.alarm.NC
.
.
5.=.Heat.pump
.
.
6.=.Zone.2.valve.
.6.
Luminous.bar.indicating.presence. 0.=.Disabled.
=.
=.
1
.
of.voltage.
1.=.Enabled
.
7.
Allocation.of.SIME.HOME.channels.
..
0.=.Not.assigned
.
=.
=.
1
..
.
1.=.Circuit.1.
.
.
2.=.Three-zone.circuit
.
8.
Fan.rpm.Step.ignition.
0,0.....81.
rpmx100. 0,1 from.0,1.to.19,9. 0,0
.
.
.
.
1 from.20.to.81
.
9.
Long.chimneys.
0.....20.
%.
1.
0
.
10. Remote.control.option.setting
..
1.=.SIME.HOME
.
=.
=.
1
..
.
2.=.CR.53.
.
.
3.=.RVS.43.143
.
.
4.=.RVS.46.530
.
.
5.=.RVS.61.843
.11. Correction.values.external.sensor. -5.....+5.
°C.
1.
0
.
12. Backlighting.duration
.
--..=.Always
.
sec..x.10.
1.
3
..
.
0.=.Never.
..
.
1.....199
.
.
13. Modulating.pump.speed
.
--.=.None
.
%.
10.
Au
..
.
Au.=.Automatic.mod..
..
.
30...100.=..%.Settable..
.
.
..................modulation
.14. Setting.second.input.TA.
.
--.=.Contact.TA
.
--.
--.
--
.
.
5...160.=.Input.0...10VDC
.15. Cascade.address.
.
--.=.Not.enabled.
.
--.
1.
--
.
.
0.=.Master
.
.
1...7.=.Slaves
.16. ModBus.address.
.
--.=.Not.enabled.
.
--.
1.
--
.
.
1...31.=.Slaves
.17. ModBus.communication.configuration...1.....30..
--.
1.
25
.19. Type.circuit..
0.=.Two.zones..
--.
--.
0
.
.
1.=.Three.zones
D.H.W. - HEATING
PAR. DESCRIPTION...
RANGE.
UNIT.OF.
INC/DEC.. DEFAULT
.
.
.
MEASUREMENT. UNIT.
SETTING
20.
Minimum.heating.temperature.Zone.1... PAR.64.OEM.....PAR.21.
°C.
1.
20
21.
Maximum.heating.temperature.Zone.1... PAR.20.....PAR.65.OEM.
°C.
1.
80
22.
Heating.curve.slope.Zone.1...
3.....40.
--.
1.
20
23.
Minimum.heating.temperature.Zone.2... PAR.64.OEM.....PAR.24.
°C.
1.
20
24.
Maximum.heating.temperature.Zone.2... PAR.23.....PAR.65.OEM.
°C.
1.
80
25.
Heating.curve.slope.Zone.2...
3.....40.
--.
1.
20
26.
Minimum.heating.temperature.Zone.3... PAR.64.OEM.....PAR.27.
°C.
1.
20
27.
Maximum.heating.temperature.Zone.3... PAR.26.....PAR.65.OEM.
°C.
1.
80
28.
Heating.curve.slope.Zone.3...
3.....40.
--.
1.
20
29.
∆t.heating.circuit.
10.....40.
°C.
1.
20
30.
Post-circulation.heating.time...
0.....199.
Sec..
10.
30
31.
Maximum.heating.capacity...
30.....100.
%.
1.
100
32.
Zone.1.pump.activation.delay...
0.....199.
10.sec..
1.
1
33.
Start-up.delay...
0.....10.
Min..
1.
3
34.
Additional.source.activation.threshold... --.,.-10.....40.
°C.
1.
“-.-”
35.
Boiler.antifreeze...
0.....+20.
°C.
1.
3
36.
External.sensor.antifreeze...
-5.....+5.
°C.
1.
-2
37.
Band.saturation....
--..=.
Disabled.
%.
1.
100
.
flowmeter.modulation...
0.....100.
38.
D.H.W..post-circulation.time..
0.....199.
Sec..
1.
0
39.
Anti-legionella..
0.=.
Disabled.
--.
--.
0
.
(only.D.H.W.tank)).
1.=.
Enabled
GAS
MODEL
PAR 1
.
.
.
.
Single.(70.R.ErP)
.
58
. METHANE
.
.
(G.20)
.
.
.
Sequence/cascade.
.
61
.
.
.
..
.
.
.
Single.(70.R.ErP)
.
59
.
.
.PROPANE
.
.
(G.31)
.
.
.
Sequence/cascade.
.
63
.
.
.
.