14
7 DESCRIPTION OF THE APPLIANCE
7.1
Characteristics
Brava Slim 30 BFR
are last generation low temperature wall
mounted boilers which
Sime
has produced for heating ONLY.
The model
30 BFRi
is designed for installation in rooms, while
model
30 BFRe
is designed specifically for outdoor installation,
protected against atmospheric agents. The main elements
choices made by
Sime
for the
Brava Slim 30 BFR
boilers are:
– the atmospheric burner combined with a copper heat
exchanger for heating and a rapid heat exchanger for DHW
– the sealed combustion chamber, with respect to the room
where the boiler is installed
– the command and control microprocessor electronic board
provides efficient management of both heating and hot water
production. It can also be connected to a remote control
with an Open Therm protocol or to room thermostat and/or
external sensor. If connected to an external sensor, the boiler
temperature varies on the basis of the external temperature
according to a selected optimal climatic curve providing
significant energy and economic savings.
Other special features of the
Brava Slim 30 BFR
boilers are:
– the anti-freeze function which activates automatically if the
temperature of the water inside the boiler falls below the
threshold of the value set at parameter "PAR 10" and , if there
is an external sensor, if the external temperature falls below
the threshold of the value set at parameter "PAR 11"
– the anti-blocking function of the pump and diverter valve, this
activates automatically every 24 hours if no request for heat
has been made
– the chimney sweep function lasts 15 minutes and makes the
job of the qualified technician easier when measuring the
parameters and combustion efficiency
– screen display of the operating and self-diagnostic
parameters with error code display when the fault occurs.
This makes repair interventions easier and allows appliance
operation to be restored correctly.
7.2
Check and safety devices
The
Brava Slim 30 BFR
boilers are equipped with the following
check and safety devices:
– thermal safety thermostat 100°C
– 3 bar (300 kPa) relief valve
– heating water pressure transducer
– delivery sensor.
NOTE:
the proper fan operation of this boiler is checked
electronically from the control panel. Then the use of an air
pressure switch is not required.
d
IT IS FORBIDDEN
to commission the appliance with safety devices which
do not work or which have been tampered with.
a
WARNING
Safety device may only be replaced by professional
qualified personnel using
Sime
original spare parts.
7.3
Identification
The
Brava Slim 30 BFR
boilers can be identified by means of:
1 Packaging label:
this is located on the outside of the
packaging and provides a code, the serial number of the
boiler and the bar code
2 Technical Data Plate:
this is located inside the front panel of
the boiler and provides the technical specification, appliance
performance and any other information required by law.
1
2
1
2
Fig. 8
KEY:
1
Packaging label
2
Technical Data Plate
m
CAUTION
Tampering with, removing or failing to display the
identification plate or carrying out any other operation
which does not allow safe identification of the product
or which may hinder installation and maintenance
operations.
Содержание BRAVA SLIM 30 BFR
Страница 4: ...4 ...
Страница 46: ...46 12 EXPLODED VIEWS Brava Slim 30 BFRi ...
Страница 47: ...47 Brava Slim 30 BFRe ...
Страница 48: ...48 Brava Slim 30 BFRi Brava Slim 30 BFRe ...
Страница 49: ...49 Brava Slim 30 BFRi Brava Slim 30 BFRe ...
Страница 56: ...56 ...
Страница 57: ...57 ...
Страница 58: ...58 ...
Страница 59: ...59 ...