74
EN
5.8
Plumbing connections
The dimensions of the water fittings of
Sime
ALU HE
boilers are
given below.
M
R
M
R
As
F
E
B
A
C
D
Fig. 16
Description
ALU HE
80
116
160
200
240
280
A (mm)
838
838
838
1089
1089
1089
B (mm)
180
180
180
238
238
238
C (mm)
175,5
175,5
175,5
175,5
175,5
175,5
D (mm)
424,5
424,5
424,5
424,5
424,5
424,5
E (mm)
678
678
678
678
678
678
F (mm)
384
384
384
384
384
384
M - Boiler
delivery
PN10
DN50
PN10
DN50
PN10
DN50
PN10
DN50
PN10
DN50
PN10
DN50
R - Boiler
return
PN10
DN50
PN10
DN50
PN10
DN50
PN10
DN50
PN10
DN50
PN10
DN50
As - Siphon
fitting
Ø15
mm
Ø15
mm
Ø15
mm
Ø15
mm
Ø15
mm
Ø15
mm
5.9
Condensate outlet/collection
Fig. 17
m
CAUTION
– The condensate outlet duct must be airtight,
suitably sized to that of the siphon and must not be
restricted at any point.
– The condensate outlet must be constructed in full
compliance of the National or Local regulations in
force.
m
CAUTION
– It is recommended that a condensate neutralising
unit be provided and the pipework should have a
downward angle of at least 3%.
– Before commissioning the appliance, fill the siphon
with water.
5.10 Gas supply
Boiler connection to the gas mains must be carried out in full
compliance with installation Standards in force.
Before connecting the boiler to the gas mains, the user must
ensure that:
– the type of gas is correct for the appliance
– the pipes are clean
– the gas supply pipe is the same size as or larger than the one
on the boiler fitting (G 1”) and has a load loss of less than or
equal to that contemplated between the gas mains and the
boiler.
G
G
E
B
A
C
D
Fig. 18
Description
ALU HE
80
116
160
200
240
280
A (mm)
838
838
838
1089
1089
1089
B (mm)
85
85
85
158
158
158
C (mm)
529
529
529
524,5
524,5
524,5
D (mm)
71
71
71
75,5
75,5
75,5
E (mm)
872
872
872
870,5
870,5
870,5
G - Gas supply
Ø 1" G Ø 1" G Ø 1" G Ø 1" G Ø 1" G Ø 1" G
a
WARNING
Once installation has been completed, check that
the joints are air tight as indicated in the installation
Standards.
m
CAUTION
It is recommended that the gas line has a suitable
filter.
m
CAUTION
If the gas supply is changed from G20 to G31, mark the
box on the TECHNICAL DATA PLATE.
Marking is
OBLIGATORY
only for models
ALU HE
80
,
116
,
160
and
200
.
X
G31 - 37 mbar