Burner adjustments
The suggested adjustments for the operation of the combinable burners installed at sea level are shown in the table.
Description
Model
Code
Nozzle
Pulverisation
angle
Pump
pressure
(bar)
NOx class
Absorbed
electrical
power (*)
(W)
Type
GPH
RONDÒ
/
ESTELLE 4 ErP BE
SIME FUEL 25 EV
(Standard
version)
8118500
DANFOSS
0,55
60°H
12
3
201
RONDÒ
/
ESTELLE 5 ErP BE
SIME FUEL 35 EV
(Standard
version)
8118501
0,65
190
RONDÒ
/
ESTELLE 6 ErP BE
SIME MACK 6
ErP BE
8099157
FLUIDICS
1,00
80°HF
263
RONDÒ
/
ESTELLE 7 ErP BE
SIME MACK 7
ErP BE
8099158
1,25
11,2
260
(**)
Values obtained during operation
When the burner is installed at altitudes up to maximum 1300 m.a.s.l., due to the lower air density, the factory adjustments for the
burner must be modified as follows:
– Keep the nozzle mounted in the factory
– Do not vary the position of the combustion head
– Gradually reduce the pump pressure to reduce the fuel flow rate
– Adjust the air shutter by taking the following readings:
- CO
2
(%)
- CO (ppm) (as per the regulations in force)
- Bacharach index (≤ 0,5)
- Flue gas temperature.