Electrical wiring
20127402
22
GB
7.6
Automatic pre-heating deactivation
It is possible to disable the pre-heater function in automatic mode
by pressing the reset button of the control box.
Tab. G
When the pre-heating is disabled, the pre-heating remains off un-
til:
–
a lockout occurs
–
the main supply voltage is interrupted
–
there is a stop due to intermittent operation.
The deactivation of the automatic pre-heating function is not lost
if the switching off test function is active or if the heat request
thermostat opens.
7.7
Post-purging
Post-purging is a function that allows you to maintain the air purg-
ing even after the burner is switched off in the absence of the heat
request for a pre-set time.
The burner switches off the flame when the heat request thermo-
stat opens, cutting off the fuel supply to the valves.
The post-purging function is not performed:
after a lockout
if the heat request is interrupted during pre-purging.
Post-purging occurs:
if the heat request is interrupted during the safety time;
if the heat request is interrupted during normal operation.
NOTE:
If during post-purging there is an extraneous light or a para-
site flame the burner goes into lockout after 25 seconds.
If during post-ventilation there is a new heat request, the
post-purging time is halted, the fan motor stops and a new
burner operating cycle starts.
Sequence of pre-heating deactivation
Colour of the led of the button
Allow the disabling of the pre-heating only when there is no lockout or fault
-
Allow the disabling of the pre-heating using the reset button.
-
Supply the burner and simultaneously keep pressed the reset button 3 seconds.
RED
Release the reset button within 3 seconds.
OFF
The burner will start disabling the pre-heating only if the reset button is released with-
in 3 seconds.
-
Содержание 8099157
Страница 2: ...Istruzioni originali Translation of the original instructions...
Страница 30: ......
Страница 58: ......
Страница 59: ......
Страница 60: ...Con riserva di modifiche Subject to modifications...