4.1 COMBUSTION ADJUSTMENT

In conformity with Efficiency Directive 92/42/EEC the application of the burner on the boiler, adjustment and test-
ing must be carried out observing the instruction manual of the boiler, including verification of the CO and CO

2

concentration in the flue gases, their temperatures and the average temperature of the water in the boiler.
To suit the required appliance output, fit the proper nozzle, then adjust the pump pressure and the air damp-
er opening in accordance with the following table.

ADJUSTMENTS CARRIED OUT IN FACTORY FOR SIME BOILERS

The values shown in the table are measured on a SIME boiler (as per EN 267).
They refer to 12.5% CO

2

 at sea level and with light oil and room temperature of 20 °C.

Table B

APPROXIMATE ADJUSTMENTS FOR INSTALLATION ON OTHER BOILERS

The values shown in the table are measured on a CEN boiler (as per EN 267).
They refer to 12.5% CO

2

 at sea level and with light oil and room temperature of 20 °C.   

BOILER

BURNER

Nozzle

Pump

pressure

Burner

output

Air damper

adjustment

Code

Model

GPH

Angle

bar

kg/h 

±

 4%

Set-point

Rondò-Estelle 3

8099000

MACK 3

0.55

60° S

12

2.1

3.7

Rondò-Estelle 4

8099010

MACK 4

0.75

60° W

12.5

2.9

2.9

Rondò-Estelle 5

8099030

MACK 5

0.85

60° W

14

3.5

3.8

4.2 NOZZLES RECOMMENDED:

Monarch type R - NS ;   Delavan type W-E
Steinen type H - Q ;   Danfoss type H - S.

MAINTENANCE POSITION

Access to the combustion head, electrodes and nozzle, (see fig. 10).

Remove the burner out of the boiler, after loosing the fixing nut to the flange.

Hook the burner to the flange (1), by removing the combustion head (2) after loosing the fixing screws (3).

Remove the electrodes assembly (5) from the nozzle-holder (4) after loosing its fixing screw (

B

, fig. 11,

page 7).

Screw the nozzle (6).

  M

o

d

e

  

Nozzle

Pump

pressure

Burner

output

Air damper

adjustment

GPH

Angle

bar

kg/h 

±

 4%

Set-point

M

A

C

K

 3

0.40

80°

10

1.4

1.7

0.40

80°

12

1.5

1.8

0.50

60°

12

1.9

2.4

0.55

60°

13

2.2

3.5

M

A

C

K

 4

0.55

60°

11

2.0

1.6

0.60

60°

12

2.3

1.7

0.65

60°

12

2.5

2.2

0.75

60°

12

2.9

2.5

0.85

60°

11.5

3.2

3.2

M

A

C

K

 5

0.75

60°

11.5

2.8

2.2

0.85

60°

12

3.3

2.5

1.00

60°

12.5

3.9

3.6

E9155

2

5

4

Fig. 10

1

3

6

Содержание 8099000

Страница 1: ...iften Installation use and maintenance instructions Oil burners Br leurs oul Stookoliebranders CODE MODEL MODELE TYPE 8099000 SIME MACK 3 514 T1R 8099010 SIME MACK 4 515 T3R 8099030 SIME MACK 5 515 T5...

Страница 2: ...4...

Страница 3: ...aulic systems 4 3 3 Electrical wiring 5 4 WORKING 6 4 1 Combustion adjustment 6 4 2 Nozzles recommended 6 4 3 Electrodes setting 7 4 4 Air damper adjustment 7 4 5 Pump pressure 7 4 6 Fuel heating 7 4...

Страница 4: ...7A 2850 rpm 298 rad s Capacitor 4 F Ignition transformer Secondary 8 kV 16 mA Pump Pressure 7 15 bar Absorbed electrical power 0 165 kW 0 185 kW 0 8 0 0 4 Pressure in the combustion chamber mbar Light...

Страница 5: ...ng gasket holes 5 Fix the ange 1 to the boiler door 4 using screws 2 and if necessary the nuts 3 interposing the insulating gasket 5 see g 3 Model A B C D E F G MACK 3 268 229 208 86 89 170 10 MACK 4...

Страница 6: ...non return valve is required This solution however is less safe than previous one due to the possibility of leakage of the valve It is necessary to install a filter on the fuel supply line The standar...

Страница 7: ...shut down of the burner by opening the ther mostats CONTROL BOX To remove the control box from the burner loosen screw A fig 8 and pull to the arrow direction after removing all components the 7 pin p...

Страница 8: ...nd room temperature of 20 C BOILER BURNER Nozzle Pump pressure Burner output Air damper adjustment Code Model GPH Angle bar kg h 4 Set point Rond Estelle 3 8099000 MACK 3 0 55 60 S 12 2 1 3 7 Rond Est...

Страница 9: ...recommended to proceed as follows Adjust the air damper as indicated in the table Mount the cover Check smoke number and CO2 Should it become necessary to modify the air output remove the cover by loo...

Страница 10: ...s Clean the filter in the oil suction line and in the pump Clean the photoresistance see fig 9 page 5 Check for correct fuel consumption Replace the nozzle see fig 10 page 6 and check the correct posi...

Страница 11: ...SOLUTION All led are off and the burner does not start Lack of electrical supply Check presence of voltage in the L1 N clamps of the 7 pin plug Check the conditions of the fuses Check that thermostat...

Страница 12: ...Fonderie Sime S p A via Garbo 27 37045 Legnago Vr Italy Tel 39 0442 631111 Export Division fax number 39 0442 631293 Sime Service fax number 39 0442 631292...

Отзывы: