02

2.3 Input power factor correction (Active PFC)

The power factor at 50% load shall be 

 0.9 at 230V input voltage.

2.4 Input current harmonics

When the power supply is operated in 90-264 VAC of Sec. 2.1, the input harmonic current drawn on the power 
line shall not exceed the limits set by IEC61000-3-2 Class A and GB17625.1 standards. The power supply shall 
incorporate universal power input with active power factor correction.

2.5 Dropout

An AC line dropout of 17mS or less shall not cause any tripping of control signals or protection circuits. If the 
AC dropout lasts longer than 17mS, the power supply should recover and meet all turn on requirements. The
power supply shall meet the regulation requirement over all rated AC voltages, frequencies, and output loading 
conditions. Any dropout of the AC line shall not cause damage to the power supply. An AC line dropout is 
defined as a drop in AC line to 0 VAC at any phase of the AC line for any length of time.

3.1 Output current / loading

3.2 DC voltage regulation, ripple and noise

The following table defines power and current rating. The power supply shall meet both static and dynamic 
voltage regulation requirements for minimum load condition.

The power supply output voltages must stay within the following voltage limits when operating at steady state 
and dynamic loading conditions. All outputs are measured with reference to the return remote sense (Returns) 
signal. The +5V, +3.3V, +12V, -12V and +5VSB outputs are measure at the power supply connectors references 
to Returns. The +5V and +3.3V is measured at its remote sense signal (+5VS, +3.3VS) located at the signal 
connector. 

Table 2– Output Loads Range 1

Note 1: Maximum continuous total DC output power should not exceed 600W.

3. DC output specification

Output Voltage

Max. Load

Min. Load

Max. Combined

Total Output

+5V

25A

1A

170W

600W

+3.3V

25A

1A

+12V

49A

1A

-

-12V

0.8A

0A

-

+5VSB

3.5A

0.1A

17.5W

Table 3 – Regulation, ripple and noise

Output Voltage

Load Reg.

Line Reg.

Ripple & Noise

+5V

+/-5

+/-1

50mV

+3.3V

+/-5

+/-1

50mV

+12V

+/-5

+/-1

120mV

-12V

+/-5

+/-1

120mV

+5VSB

+/-5

+/-1

50mV

Содержание GEMINI GM600-G

Страница 1: ...4hour fully continuous power output PS2 mini redundant power with 150mm W x 85mm H x 180mm D 80 PLUS Gold Certified Active PFC full range 1 1 redundant configuration Hot swappable design Convenient pu...

Страница 2: ...ading or performing maintenance on your system A copy of this manual can also be downloaded from our website at Installation and system optimization guide Specification General AC input specifications...

Страница 3: ...temperature range The peak inrush current shall be 30 60A 115 230 VAC 25 per module when cold start and less than the rating of its critical components including input fuse bulk rectifiers and surge...

Страница 4: ...hase of the AC line for any length of time 3 1 Output current loading 3 2 DC voltage regulation ripple and noise The following table defines power and current rating The power supply shall meet both s...

Страница 5: ...the on off of the power supply Ripple and Noise shall be measured using the following methods a Measurements made differentially to eliminate common mode noise b Ground lead length of oscilloscope pr...

Страница 6: ...fromAC being applied to 5VSB is being within regulation Delay fromAC being applied to all output voltages being Within regulation All main output voltage stay within regulation after loss ofAC Delay...

Страница 7: ...ing of power supply 4 1 Over power protection Each hot swap module has respective OVP circuit Once any power supply module shut down in a latch off mode while the output voltage exceeds the over volta...

Страница 8: ...tch off mode when the output voltage is short circuit Input leakage current from line to ground will be less than 3 5mA rms Measurement will be made at 240 VAC and 60Hz Operating Temperature Range Non...

Страница 9: ...to two power supplies may be on a single AC power source Extraction The AC power will be disconnected from the power supply first and then the power supply is extracted from the sub system This could...

Страница 10: ...ddressing pins A0 and A1 on the power supply module The circuits inside the power supply shall derive their power from the 5VSB bus Device s shall be powered from the system side of the 5VSB device No...

Страница 11: ...PEED READ_POUT READ_PIN PMBus_REVISION MFR_ID MFR_MODEL MFR_ REVISION MFR_SERIAL MFR_VIN_MIN MFR_VIN_MAX MFR_POUT_MAX USER_DATA_00 Reserved Reserved Reserved Reserved READ_AC_PFC READ_AC_FREQUENC SMBu...

Страница 12: ...erved Reserved Reserved READ_AC_PFC READ_AC_FREQUENC Meaning 239 88 V 2 499A 12 100 V 24 000A 38 5 12400 rpm Reserved 250 00 W 600 0 W 1 SilverStone SST GM600 G A0 201312120001 100 VAC 240 VAC 600W St...

Страница 13: ...ave12V Meaning Default 0 Default 0 Default 0 Default 0 Default 0 Default 0 PS_OFF 0 PS_ON 1 AC OK 0 AC Fail 1 PMBus command protocol for the two steps Figure 8 2 3 1 The first step is master device se...

Страница 14: ...he Part Stress Analysis method of MIL 217F or Bell core RPP The calculated MTBF of the power supply shall be greater than 100 000 hours under the following conditions Full rated load 120V AC input Gro...

Страница 15: ...NO G11223840...

Отзывы: