INS376 MESH-HBND  (Issue 03)

PLEASE READ THESE INSTRUCTIONS BEFORE INSTALLING THE PRODUCT
NOTE: MESH-

HBND

 is compatible with any qualifi ed Bluetooth mesh components and commissioning tools. 

We recommend Silvair Commissioning as a reliable solution.

MESH-HBND

Ceiling High Bay (Narrow) Passive Infra Red 

(PIR) Occupancy Detector & Photocell

Input: 100-240 Vac  50/60Hz                             

This MESH-HBND High Bay (Narrow Detection) 

Lighting Control can be mounted directly onto 

solid ceilings or onto a range of different mounting 
boxes. Confi gurable for any room occupancy 
style, via the Silvair  Platform (App and Web).

INSTALLATION

To be installed by a competent person with 

reference to BS 7671 or equivalent local 

standards. If in doubt consult a qualifi ed 

electrician.

•  Plan where the MESH-HBND is to be located 

(see diagram 1). Switch off supply and check 

for hidden cables and pipes. 

•  The MESH-HBND should be connected as 

shown in diagram 2:

  L - Live in.   N - Neutral in.
•  Knockout or drill the appropriate holes on the 

mounting plate for attaching the plate to the 

ceiling or back box (if applicable). Feed cables 

through the appropriate (side or rear) entry hole. 

Screw the back mounting plate to the ceiling or 

back box via the mounting holes. Wire the cables 

into the sensor head block terminal. Push the 

sensor head onto the mounting plate and align 

the side clips with the slots on the sensor heads.

OPERATION

To check the operation of the MESH-HBND:
•  Turn on the supply then after 20 seconds if the 

sensor has recognised movement of a person 

within its zone of detection the integral red 

LED on MESH-HBND will stay illuminated for 4 

seconds before the red LED turns off.

•  Thereafter, every time movement is detected 

by MESH-HBND the integral red LED will stay 

illuminated for 4 seconds. 

The control also features adjustable time out (time 

lag) control and daylight threshold control which 

are confi gured by the Silvair APP.

PRECAUTIONS

•  Do not place the MESH-HBND near heat 

sources, fans or in ventilated ceiling voids.

•  MESH-HBND can be wired in parallel (sharing 

the same Live and Neutral).

•  Do not place close to, or positioned such 

that, any light source points directly into the 

MESH-HBND. 

•  Ensure wires and cables are securely held 

within the connection terminals.

•  The MESH-HBND should be protected by a 5 

or 6 Ampere mcb or fuse.

• 

Disconnect the MESH-HBND from the 

circuit before performing insulation testing 

of the wiring circuit.

TECHNICAL DETAILS

INPUT

Voltage:

100 - 240Vac

Frequency:

50/60Hz

Max. mains current:

20mA

Standby current:

14mA

RADIO TRANSCEIVER

Operating frequencies: 2.4... 2,483 GHz
Max. output power:

+4 dBm

LUX PARAMETERS

Range:

5 - 2000 lux

OPERATING CONDITIONS 

Note: The temperature difference between the 

detection target and the background must be 

at least 4 °C.

Ambient temperature:

-20... +40 °C (lout 

20mA)

Storage temperature:

-25... +75 °C

Max. relative humidity:

0... 80%, non cond.

CONNECTORS

Terminal block 

Wire size:

0.5mm

2

 - 2.5mm

2

solid or stranded

Wire strip length:

6-7mm

Tightening torque:

0,4 Nm/4 Kgf.cm

MECHANICAL DATA

Dimensions:

63mm x 91mm x 

91mm

Weight:

113g (unpacked)

Degree of protection:

IP20

Protection class:

Built-in Class 2

Material (casing)

Flame-retardant 

polycarbonate

Finish / Colour

Matt /White (RAL 

9003)

Protection class:

Built-in Class 2

CONFORMITY AND STANDARDS
EMC emission: 

EN 301 489-1 V2.2.0,  

EN 301 489-17 V3.1.1, 

EN 55032: 2015,  

EN61000-3-2: 2014, 

EN61000-3-3: 2013

EMC immunity:

EN 301 489-1 V2.2.0,  EN 301 489-17 V3.1.1

Environment: 

Complies with WEEE and RoHS directives

CB scheme:

IEC60669-1:1998, 

IEC60669-1:1998/AMD1:1999, 

IEC60669-1:1998/AMD2:2006,  

IEC60669-2:2002, 

IEC60669-2-1:2002/AMD1:2008,

DIAGRAM 1

Suggested typical wiring

N

L

230 Vac

5A or 6A MCB

or fuse

L

N

N

L

L - Live in. N - Neutral in.

Two neutral and two live terminals

are available for easy ‘loop in’ and 

‘loop out’ connection.

DIAGRAM 2

Up to 5m

diameter

Up to 3m

NARROW 

DETECTION (ND)

Mounting height 

up to 12m

Perspective view - 

ceiling mounted

Up 

to 

15m

SPOT 

DETECTION (SP)

Mounting height 

up to 20m

Perspective view - 

ceiling mounted

Up to 28m

diameter

WIDE 

DETECTION (WD)

Mounting height 

up to 14m

Perspective view - 

ceiling mounted

5 YEAR WARRANTY

MESH-HBND comes with a 5 year  
warranty from the date of manufacture 
and is CE marked.