PLEASE READ THESE INSTRUCTIONS BEFORE INSTALLING THE PRODUCT
NOTE: MESH-CEDRP is compatible with any qualifi ed Bluetooth mesh components and commissioning tools.
We recommend Silvair Commissioning as a reliable solution.
MESH-CEDRP
Plug-in Directional Passive Infra Red
(PIR) Occupancy Detector & Photocell
Input: 100-240 Vac 50/60Hz
DANLERS Limited, Vincients Road, CHIPPENHAM, Wiltshire, SN14 6NQ, UK.
Telephone: +44 (0)1249 443377 Fax: +44 (0)1249 443388 E-mail: [email protected]
www.danlers.co.uk
Company Registered Number 2570169 VAT Registration Number 543 5491 38
11/10/19
INS374 MESH-CEDRP (Issue 03)
DIAGRAM 3
60
74
64
102
side
MESH-CESO (Not included)
HALL EFFECT / FACTORY RESET:
This function allows a reset to be carried out in order to restore the default
factory settings.
A factory reset will change the state of MESH-CEDRP from ‘provisioned’
to ‘unprovisioned’, i.e. all network settings will be lost. This functionality
is required to allow reprovisioning MESH-CEDRP where control over the
device is not functioning correctly.
TO REPROVISION:
Place a small magnet on the site of the Reset / Hall effect sensor
(see diagram 4 below). To trigger the reset the magnet must be held in
position for 5 seconds.
DIMENSIONS
STATUS LED BLINKING SEQUENCE:
MESH-CEDRP
Unprovisioned:
30ms ON
300ms OFF
MESH-CEDRP
Provisioned:
15ms ON
2000ms OFF
Factory Reset:
500ms ON 1000ms OFF
Factory Reset (initial burst):
100ms ON 1000ms OFF
MESH package received:
30ms ON
50ms OFF
Attention (from network):
500ms ON 500ms OFF
RESET ZONE (behind moulding).
Magnet to be placed over this
area for reprovisioning.
STATUS LED.
Flashes rapidly when
unprovisioned.
Flashes slowly when
provisioned.
DIAGRAM 4