Model 5495 Distributed Power Module Installation Manual
4-7
The following is the maximum current draw from the auxiliary power terminals for standby calculations. These
currents assume 24 or 60 hours of standby time, followed by 5 minutes of maximum alarm current.
•
195 mA for 24 Hour Standby Current
•
39 mA for 60 Hours of Auxiliary Standby Current
The above numbers were calculated assuming the use of 7 AH batteries at 100% of rated capacity.
The total current of the 5495, plus all items powered from it, must not exceed 6 A when the panel is in alarm. Use
Table 4-2 to ensure that the current does not exceed 6 A and, that the desired amount of standby is possible for
the battery intended for use with the 5495.