BACKPLATE

BACKPLATE

SIGN 

HOUSING

ALL INSTALLATIONS REQUIRE STANDARD TYPE 4" x 4" SQ x 2 1/8" DEEP J- BOX. 

SET ADAPTOR PLATE  ¼"- 3/8" BELOW FINISHED PANEL SURFACE

Before installing or connecting any primary power wiring,

DISCONNECT MAIN POWER SUPPLY AT THE CIRCUIT BREAKER OR FUSE.

WALL MOUNT

WALL MOUNT

1. Install J-Box 1/8"-1/4" below finished panel surface. Connect Power Module  AC wiring to
    building supply  in J-Box, using wire nuts or connectors supplied. 
 

BATTERY MODELS: BLACK:  120 277 VAC   WHITE: Common

 

AC MODELS: Non- Polarized Line in.

2. Route wire nuts to side of J-box, insert Power Module into box and secure with 2 #8-32 box
    screws.
    NOTE: Power module orientation is universal, position as required to clear connectors 
    and wire  nuts in J-box.
3. Remove back plate from sign assembly by inserting  pin (small screwdriver or allen key) 
    into 2 release holes in top edge, press down to release clips and hinge cover away from
    housing.
4. Support backplate on raised flat surface and knock out oval opening
    in center.   
    NOTE: Remove any sharp edges around opening by file or sharp metal blade. Drill  3/16"
    diameter holes at locations noted above. For additional support drill out 2 additional 3/16"
    dia holes at left and right sides on center. Locate back plate in position on wall and mark
    support holes; install wall anchors for support screws.
5. For battery backup models, connect 2-pin polarized battery plug.
6. Run LED lamp plug through backplate. Attach back cover to j-box with 2  #8-32 screws 
    supplied. Install and tighten 2 support screws. DO NOT OVERTIGHTEN.
7. Insert 2 tabs on base of sign assembly into slots in base of back cover. Connect LED lamp
    plug.
8. Hinge sign assembly into position and snap closed.

    To remove signs, repeat step 3. 

W

ALL

POWER 

MODULE

ADAPTOR

PLATE

BACKPLATE MT. SCREWS 

#8-32 SELECT LENGTH 

1/2" - 3/4"

REMOVE

K.O. FOR WIRING

DRILL OUT 3/16" DIA

IN TWO PLACES TO 

MATCH

 J-BOX LOCATION

DRILL 3/16" IN TWO PLACES

FOR ADDITIONAL WALL MT. 

SUPPORTS

USING SCREW ANCHORS

1 1/2" SQ.

 EXTENSION

AC POWER 

INPUT

       120/277 VAC

POWER MODULE
MOUNT SCREWS

#8-32 (2 REQD)

POLARIZED

LED LAMP

PLUG

GRD

J- BOX

4" x 4" 

x 2 1/8"

LOWER 
BRACKET

SPACER

TEST

PANEL

DIFFUSER 

LENS

TEST SWITCH
AND LED

INSULATOR

PLUG
CONNECTOR

WIRING TO
POWER 
SUPPLY

TEST PANEL ASSEMBLY

Series RPROBB & RPROAC

Rapier Open Face Die Cast LED System
Battery Backup & AC Models

03.15.03

Содержание RPROAC Series

Страница 1: ...ear gas or electric heaters Mount and secure exit sign at a location and height to avoid ready access and tampering by unauthorized persons Exception Floor proximity installations The use of accessory equipment is not recommended by the manufacturer and may cause an unsafe condition Do not use this equipment for other than intended use IMPORTANT SAFEGUARDS READ AND FOLLOW ALL SAFETY INSTRUCTIONS S...

Страница 2: ...arp metal blade Drill 3 16 diameter holes at locations noted above For additional support drill out 2 additional 3 16 dia holes at left and right sides on center Locate back plate in position on wall and mark support holes install wall anchors for support screws 5 For battery backup models connect 2 pin polarized battery plug 6 Run LED lamp plug through backplate Attach back cover to j box with 2 ...

Страница 3: ...ur 8 32 screws and detach two corner brackets and one lower bracket Retain all screws 3 Remove lens diffuser and place on scratch free surface LED panel and test panel assembly in battery backup models only can be left in place 4 Place sign face down on raised wooden blocks or other scratch free surface and carefully knock out selected chevron with hammer and small punch 5 Place upper edge of lens...

Страница 4: ...Disconnect wire nuts or push nut connectors to AC line inputs To replace with new Power Module reverse this sequence 220 VFWAvenue Grasonville MD21638 TEL 410 827 8300 Fax 410 827 8866 sales signtexinc com www signtexinc com Signtex Inc LIGHTING BATTERY DIAGNOSTIC FUNCTIONS Microprocessor programmed to perform tests as follows Continuous Monitoring w 1 Second Sampling Lamp Connections Transfer swi...

Отзывы: