Document Reference: X-0036-01-07 Cadmus & Ratifi Operating Manual
Drawn: 13/11/2020
Page 12 of 66
1.9
Configuration Wizard
1.9.1
Main Tab.
The main tab contains parameters related to the general functionality of the Cadmus device.
Parameter Name
Description
Options
ENABLE/DISABLE
Changes the state of the Cadmus device
ON = Active Monitoring State , OFF = NAP mode
(device is sleeping)
In NAP mode the device will connect every 90
minutes to check if a new configuration packet has
been queued for the device on the cloud.
LOCATION
Location description text.
Maximum 32 characters. (e.g. Kitchen, Warehouse
1, Pharmacy, etc)
SERIAL NUMBER
Unique Factory set serial number.
Read Only.
MAC ADDRESS
Unique MAC address associated to the WiFi hardware within the device.
Read Only.
STORE RATE
Determines how often the device stores the sensor inputs to on-board memory. Default value = 10
minutes. The device has a fixed sample rate of 1 minute. If a sensor alarm occurs the device will store
the input within 60 seconds and force an upload, before returning to the configured store rate. So
irrespective of store rate, alarms will be notified within 60 seconds.
Available Settings.
1, 2, 3, 5, 10, 15, 30, 45, 50, 60 minutes.
UPLOAD RATE
Determines how often the device makes connection to a WiFi network and uploads its data to the cloud.
Default value = 30 minutes. If a sensor alarm occurs the device will connect within 60 seconds of the
alarm occurring, make its upload and then return to the configured upload rate.
Note. Ratifi has a built-in late alarm, which triggers if a device is not received. The default late alarm
period is 120 minutes. When configuring a device will a “UPLOAD RATE” >= 120 minutes. The “LATE
ALARM TRIGGER” should be extended. See section
Available Settings.
5, 15, 30, 45, 60, 90, 120, 180, 360, 720, 1440
minutes.
CALIBRATION PERIOD
All devices contain the last calibration date. The device will automatically send reminders via the cloud
when calibration is less than 30 days away, and when the calibration expires.
Available Settings.
OFF, 6, 12, 18, 24, 36 months.
Setting OFF will disable all warnings.
AUDIBLE ANNUNCIATOR
When a sensor alarm is active the device will bleep an internal bleeper twice every 15 seconds.
OFF = bleeper disabled.
ON = bleeper active on sensor alarm.
RESET BATTERY LIFE
INDICATOR
All devices contain the date the internal batteries were last changed. Due to the battery technology
used it is not possible to monitor battery life based on the battery voltage, so a coulomb counting
method is implemented. For this method to accurately determine the battery state, the user must
inform the device when the batteries have been replaced.
NO = Do not send battery reset to device.
YES = Reset battery information and set battery
replaced date.
If a device is externally powered the device will
ignore the reset.
1.9.1.1
Battery Life Considerations.
The tables below give an estimated battery based on “Store Rate and Upload Rate” settings from +10 to +40°C ambient temperatu
re for the device enclosure. Low
battery indicator email will trigger when 20% capacity has been reached. Note. Battery life will be reduced below the values stated before if the Wi-Fi network has
poor connection or there are a high number of sensor alarms occurring. Values below are only accurate when the device is fitted with new CADMUS-ACC-01 batteries
only.
Store Rate
Upload Rate
Battery Life
1 min
5 mins
0.28 years
1 min
15 mins
0.45 years
1 min
30 mins
0.52 years
5 mins
5 mins
0.43 years
5 mins
15 mins
0.96 years
5 mins
30 mins
1.39 years
Store Rate
Upload Rate
Battery Life
5 mins
60 mins
1.79 years
10 mins
30 mins
1.75 years
10 mins
60 mins
2.44 years
15 mins
15mins
1.18 years
15 mins
30 mins
1.92 years
15 mins
60 mins
2.77 years
Store Rate
Upload Rate
Battery Life
30 mins
30 mins
2.12 years
30 mins
60 mins
3.22 years
30 mins
120 mins
4.35 years
45 mins
45 mins
2.87 years
45 mins
90 mins
4.16 years
60 mins
60 mins
3.50 years