Scope

The scope of this technical manual includes four phases; first 

it relies on helping the end user arrange / prepare the site 
where the MicroDC is going to be installed. Second it explains 
how the MicroDC should be properly handled, installed, 
connected and operated. Third there is a maintenance guide 
showing the maintenance procedure needed to be followed 
in order to extend the MicroDC operating life. Forth there is 
a troubleshooting guide on how to handle possible misuses 
or other issues including a detailed FAQ (Frequently Asked 
Questions) table.

Part list of 24U Micro Data Center

Number

Part Number

Description

Quantity

1

02 1035 M 00

24U

 40

 inches Solid Side Panel

2

2

484 16023A

Heavy Duty Castor Set

2

3

484 16023B

Heavy Duty Castor Set without break

2

4

021607M00

24U 

32

 inches Solid Door with Gasket

2

5

021610M00

24U Horizontal Organizer with Bendradius

2

6

021740P00

19" Mounting Rails

4

7

021874M00

Micro DC Top/Bottom Covers

1

8

021894M00

19" Air Flow Driver

1

9

021895M00

24U IP54 

32x40 

inches Aluminum Case

1

10

025124H00

2 kW Air Conditioner

1

11

484073335012

M5x12 Screws

14

 1182,25 

 800 

 1737,25 

 1000 

A

10

4

4

1

9

DETAIL A 

SCALE 1 : 5

11

6

REVISIONS

ZONE

REV.

DESCRIPTION

DATE

APPROVED

A

İLK ÜRETİM

26.09.2014

ÖĞE NO. PARÇA NUMARASI

Tanım

MİKT.

1

02 1035 M 00

24U 1000mm SOLID YAN KAPAK MONTAJI

2

2

484 16023 AABA

Sugatsune GX-60-N12S ( Frenli Tekerlek )

2

3

484 16023 BABA

Sugatsune GX-60-N12 ( Frensiz Tekerlek )

2

4

021607M00

24U 800mm CONTALI SOLID KAPI MONTAJI EMS

2

5

021610M00

24U BENRADUSLU DİKEY ORGANİZER MONTAJI

2

6

021740P00

ALM.24U 19" AĞIR TİP TAŞIYICI DİKME   

4

7

021874M00

MİCRO DC ALT-ÜST KAPAMA PANELİ MONTAJI

1

8

021894M00

19"  HAVA YONLENDİRMELİ KAPAMA PANELİ MONTAJI 1

9

021895M00

IP54 24U 800X1000 ALM KABİNET ŞASESİ

1

10

025124H00

4KW STULZ KILIMA

1

11

484073335012

CİVATA M5*12 TSB KOMBİ (TORK SİLİNDİRİK BAŞ) EJOT  14

DRAWN

CHK'D

MFG

Q.A

FINISH:

KESKİN KENAR 

VE ÇAPAK 

OLMAYACAKTIR

NAME

SIGNATURE

DATE

TITLE:

DWG NO.

SCALE:1:50

SHEET 1 OF 1

A3

 mm 

WEIGHT:      

   Kg

Tanju BAHADIR

IP54 24U 800X1000 4KWE STULZ KILIMALI ALM KABİNET

The contents of this dovument are property of CANOVATE and sould not be copied, reproduced or disclosed to a third party without written consent of the proprietor.KORAY

Alemdağ Cad. No:169 81257 Ümraniye-İSTANBUL

www.canovate.com

ELEKTRONİK ENDÜSTRİ TİCARET A.Ş.

Bu dökümanın içeriği CANOVATE'in mülkiyetinde olup, yazılı izin alınmadan kopya edilemez, aynı biçimde oluşturulamaz ve üçüncü şahıslara açıklanamaz.

26 Eylül 2014 Cuma 12:58:51

E:\pdmview\canovate\Standart Urunler\05-Micro Datacenter Kabinetler\CAD Files\

13 Ağustos 2013 Salı 10:52:23

26 Eylül 2014 Cuma 12:59:14

CPJ-M-2480A-T4K-EMS-01

UNLESS OTHERWISE SPECIFIED:

DIMENSIONS ARE IN MILLIMETERS

Surface finish:   µ 

Linear      :               DIN 7168-m

Angular   :                DIN 7168-m

Hole         :               DIN 7168-m

Surface Area :       

  m²

E:\pdmview\canovate\Standart Urunler\05-Micro Datacenter Kabinetler\CAD Files\

±1.2

±0.8

>315-1000 >1000-2000

±0.5

±0.2

>30-120

±0.3

>0-6

±0.1

TOL.

OLCU

>6-30

>120-315

DIN 7168-m

GENEL TOLERANSLAR 

CPJ-M-2480A-T4K-EMS-01 

MATERIAL:

Thickness

26.09.2014

www.signamax.com

Micro Data Center Technical Manual 4

Содержание MicroDC

Страница 1: ...Technical Manual of Micro Data Center Data Centers for the EDGE www signamax com ...

Страница 2: ...ing unit 9 2 3 Mains Power Supply Line 10 3 Installation 11 3 1 Required Setup Equipment 11 3 2 Cabinet Installation 11 3 3 Cooling Unit 17 3 4 Secondary Equipment 19 4 Maintenance 20 4 1 Cooling device 20 5 Troubleshooting 21 5 1 Wheels 21 5 2 Cooling 22 6 Service Log 24 7 Certificates 25 www signamax com Micro Data Center Technical Manual 2 ...

Страница 3: ...densing Install the product in a clean environment free from dust moisture flammable liquids gases and corrosive substances Whereapplicable thisproductmustbepermanentlyconnected and powered from a suitable single phase AC supply rated in accordance with the equipment data plate It must be suitably grounded and protected by a circuit breaker or fuse A residual current device commonly known as diffe...

Страница 4: ...IPTION A İLK ÜRETİM ÖĞE NO PARÇA NUMARASI 1 02 1035 M 00 24U 1000mm S 2 484 16023 AABA Sugatsune GX 3 484 16023 BABA Sugatsune GX 4 021607M00 24U 800mm CON 5 021610M00 24U BENRADUSLU 6 021740P00 ALM 24U 19 7 021874M00 MİCRO DC ALT Ü 8 021894M00 19 HAVA YONLEND 9 021895M00 IP54 24U 800X 10 025124H00 4K 11 484073335012 CİVATA M5 12 TSB K DRAWN CHK D MFG Q A FINISH KESKİN KENAR VE ÇAPAK OLMAYACAKTIR ...

Страница 5: ...d to a third party without written consent of the proprietor KORAY Alemdağ Cad No 169 81257 Ümraniye İSTANBUL www canovate com ELEKTRONİK ENDÜSTRİ TİCARET A Ş Bu dökümanın içeriği CANOVATE in mülkiyetinde olup yazılı izin alınmadan kopya edilemez aynı biçimde oluşturulamaz ve üçüncü şahıslara açıklanamaz 26 Eylül 2014 Cuma 14 14 27 E pdmview canovate Standart Urunler 05 Micro Datacenter Kab 13 Ağu...

Страница 6: ...g unit comes in two versions version one is 2KW cooling capacity version two is 3 8 KW cooling capacity The second way is to feed the cooling unit from a dedicated power line from any available electrical distribution panel It is strongly recommended to use the second option and feed the system by a separated power line In chapter 4 3 there is brief explanation on what kind of circuit breaker shal...

Страница 7: ...e generated noise mainly coming from the embedded compressor might be annoying Please avoid placing the MicroDC close to any infants Please visit the room where the MicroDC stands quite often especially after the first installation to secure that the environmental conditions meet the operating limits 2 3 Mains Power Supply Line A clean unloaded and direct single phase power supply line shall be pr...

Страница 8: ...ration Install the MicroDC in a computer room or in any other room where people are normally present only for maintenance 3 1 Required Setup Equipment The following tools are required to set up your MicroDC Pallet jack Utility knife Allen key number 4 ratchet or wrench Torx screwdriver T25 ratchet or wrench Measuring tape and pen marker able to write on metal surfaces Spirit Level hammer Flathead ...

Страница 9: ...alid whenever a transportation mishandling has damaged the MicroDC The MicroDC is standing on a wooden pallet All the way round there are lots of thick cartons used for protection of the cabinet against possible damage to the surface color Overall these carton vertical lines there is nylon or bubble nylon used for protection against dust insects or any other small similar intrusions Step 1 Remove ...

Страница 10: ...l take care not to scratch the color of the MicroDC cabinet Step 3 Remove all carton pcs surrounding the MicroDC Those cartons are loose so there is no need to use any tool at the moment Please recycle all the carton parts used for the packaging www signamax com Micro Data Center Technical Manual 10 ...

Страница 11: ...t as possible Release the brakes on the wheels if available Then grab the MicroDC gently and carefully slide it down so it can slowly move to the floor After the MicroDC has left the wooden pallet is ready to be placed at its final position Note Known the weight and size of the MicroDC it is possible that the MicroDC may tip over while moving The MicroDC must be removed from the shipping crate usi...

Страница 12: ... inch 483 or 533mm rack rails These internal mounting rails will be either center mount rails or front and rear mount rails that are designed in accordance with the EIA 310D or EIA 310E rack standard Both types are adjustable for equipment of different sizes There are two pairs of mounting rails inside the MicroDC the front pair and the rear pair The distance in between the 2 vertical rails in a s...

Страница 13: ... rails This will prevent the installer from any injures such as electrical shock 3 2 4 Mounting Hardware Optional mounting clip nuts and screws are available for mounting equipment to the mounting rails Clip nuts are a clip with a captive nut that fits over vertical rack rail holes allowing individual placement of the mounting hardware Each clip nut and screw package includes 10 clip nuts Type 10 ...

Страница 14: ...le 2KW edition According to the technical datasheet of the Air Condition Unit the maximum absorbed power is 1300W which makes a current around 6 Ampere As per the manufacturer a fuse of 10A 16A rated shall be used Please pay attention this circuit breaker must be rated tripping B with equal or more Recommended Equipment Stacking Arrangement Return Air Return Air Return Air Blowing Air Blowing Air ...

Страница 15: ...ower then it is ready and operational There is no embedded switch so after turning the external circuit breaker to ON position then the cooling device will start immediately The factory temperature setting is usually at 35 degrees Celsius 95 F Note Please refer to the respective user manual of the cooling unit for detailed information on how to operate and interfere to the default settings Inside ...

Страница 16: ...ty having Jurisdiction in the end use application Signamax offers different models of CSA Certified PDU s if required as part of Micro DC Solution They are available in single phase but also three phase power input options The units may be used in 120V 208 240V or 230V applications with almost every type of connectors including NEMA or IEC type they are available in basic type metered and with or ...

Страница 17: ... embarking on any maintenance work switch current off of the cooling unit The cooling unit is a low maintenance type so no filter change is required The main job that regularly needed to be done is to blow the internal components with compressed dry air at a maximum pressure of 4 bars the following also shall be checked regularly Job Frequency Check the external air to air heat exchanger and clean...

Страница 18: ...t able to move It is very difficult the movement of MicroDC The version does not include wheels Please unload the MicroDC to become lighter and then relocate the standing position The wheels are dirty Clean the wheels by remov ing all attached dust and dirt You may use a lubricant spray as well The brakes where available are preventing from sliding Release the brakes and then try to move the Micro...

Страница 19: ...ompressor does not work Compressor s amperometric protector failed external to the compressor where present Relay or PTC for compres sor starting failed Capacitor for compressor starting failed where pres ent Compressor motor electrical failure High pressure safety switch failed Compressor contactor failed where present This is not a malfunction of the cooling unit To verify functioning when testi...

Страница 20: ...condenser either dirty or clogged Ventilate the premises where the enclosure is installed to keep ambient temperature lower Clean the exchanger with compressed air and detergent Thermal protector inside the compressor triggered Ambient temperature over the maximum working limit Heat exchanger coil condenser either dirty or clogged Ventilate the premises where the enclosure is installed to keep amb...

Страница 21: ...mirates T 97 155 424 2722 E ME signamax com SOUTH EAST ASIA 55 UBI Ave 1 02 10 UBI 55 Singapore 408935 T 65 6925 5798 E FE signamax com CANADA 2 975 Bleams Rd Kitchener Ontario Canada N2E3Z5 T 1 519 570 3911 E CA signamax com MALAYSIA Suite 1 2 1st Floor Bangunan THK No 2A Jalan 243 Seksyen 51a 46100 Petaling Jaya Selangor Malaysia T 60 3 7873 7317 E mei signamax com SRI LANKA 49 Sri Jinarathana R...