than 4.5KA short-circuit capacity. The input plug for the Air-
Condition Unit is 6-20 Nema plug
3.8 KW edition: According to the technical datasheet of the
Air-Condition Unit, the maximum absorbed power is 2620W
which makes a current around 11.4 Ampere. As per the
manufacturer a fuse of 20A-25A rated shall be used. Please
pay attention this circuit breaker must be rated tripping B with
equal or more than 4.5KA short-circuit capacity. The input for
plug for the Air-Condition Unit is 6-20 Nema plug
After connecting the cooling unit to the Mains Power then it is
ready and operational. There is no embedded switch so after
turning the external circuit breaker to ON position then the
cooling device will start immediately. The factory temperature
setting is usually at 35 degrees Celsius / +95°F .
Note: Please refer to the respective user manual of the
cooling unit for detailed information on how to operate and
interfere to the default settings.
Inside the MicroDC there is one plastic hose. It fits
to the Air-Condition Cooling Unit, outside of the
MicroDC. It is used for any condensation water may
be produced. This pipe should be driven to the first
available drain (gutter or spout). Please avoid using a
bowl as it may be flooded and overflown!
www.signamax.com
Micro Data Center Technical Manual 15