Modbus Register Remapping
The gateway allows any of the remote register data to be remapped to a single block of
registers available at the Gateway’s Modbus ID (default is 247). This is useful for collecting a
subset of register data from multiple nodes and making it readable in a single block of registers.
Up to 1500 registers can be remapped to the gateway’s Modbus ID starting at register 5000.
To configure the remapping, first select
Modbus Register Remapping
from the
Settings
dropdown menu.
Enter the remote Modbus ID and register address to map to each gateway register and click
Write to GW
to
remap the register(s).