If the SCP 011 with a firmware version lower than V355 resp. with a Safety number
lower than S01.03.01 is integrated with Safety I/O modules in the S-DIAS system (blue
moduls), the voltage increase of the +24 V supply of the SCP 011 must not happen
later than 100 msec after the voltage supply oft he S-DIAS supply moduls, otherwise
it can happen, that the SCP 011 does not recognize the Safety I/O moduls on the
Safety bus. This results in a Safety error (error code 1009, reason code 15 in the
Safety Designer) and thus the Safety application is not started.