4.3 Environmental Conditions
Storage temperature
-10 … +70 °C
Environmental temperature
0 ... +50 °C
1)
Humidity
10-95 %, non-condensing
Installation altitude above sea
level
0-2000 m without derating
> 2000 m up to a maximum of 5000 m with derating of the maximum
environmental temperature by 0.5 °C per 100 m
Operating conditions
pollution degree 2
EMC resistance
2)
according to EN 61000-6-2 (industrial area)
EMC noise emission
2)
according to EN 61000-6-4 (industrial area)
Vibration resistance
EN 60068-2-6
3.5 mm from 5-8,4 Hz
1 g from 8.4-150 Hz
Shock resistance
EN 60068-2-27
15 g (147.15 m/s
2
)
Protection type
2)
EN 60529
protection through housing
cover: IP20
(not UL-listed)
1)
The maximum environmental temperature allowed depends on the TP connected. The ambient temperature cannot
exceed any of the permissible values.
2)
Applies only if the PIM 041-W is mounted onto the TP.