![SIGMATEK HGT 835 Скачать руководство пользователя страница 22](http://html.mh-extra.com/html/sigmatek/hgt-835/hgt-835_manual_1268125022.webp)
HGT 835
8.4“ HANDHELD CONTROL PANEL
Page 20
16.08.2018
X2:
M16 Cable Connector
The appropriate connector cables are optionally available.
See documentation for connection cables operating devices.
The
handheld
control
panel
can
only
be
operated
with
the SCP XXX Safety module!
As required by EN ISO 13850, section 4.1 and EN 60204-1, section 10.7.1, it
must be impossible to confuse a functioning handheld control panel with a
non-functioning one.
Note on the Emergency Stop function: A non-connected HGT 835 does not
have to be visibly sealed!
LED
Pin
Wire color
Function
L
Yellow
Safety Interface-H
J
Green
Safety Interface-L
G
Black
Safety Interface shield
E
Red
+24 V DC
C
Black
GND
A
Shield
ETH shield
U
White
T
Red
S
Blue
VAR_RX-
R
Pink
P
Gray
VAR_TX-
O
Yellow
ETH_RX-
N
Green
M
Brown
ETH_TX-
LED status
Meaning
LED lights green