8.4" HANDHELD CONTROL PANEL
HGT 835
16.08.2018
Page 15
The function of the key switch, confirmation switch and emergency stop switch must
be tested at least once per month.
L'interrupteur à clé, l'interrupteur de confirmation et de l'interrupteur d'arrêt
d'urgence doivent être vérifiés au moins une fois par mois!
3.2
Electrical Requirements
Supply voltage
typ24 V DC (PELV)
m24 V DC (PELV)
m30 V DC (PELV)
Supply voltage (UL)
+24-30 V DC (NEC Class 2 or LVLC)
Current consumption
Power 24 V
typically 0.35 A
(without externally connected devices)
typically 0.45 A
(with external devices connected)
Inrush current
maximum 10 A for < 50 µs
USB current load
maximum 0.5 A
For USA and Canada:
The supply must be limited to:
a) max. 5 A at voltages from 0-20 V (0-28.3 Vp) or
b) 100 VA at voltages from 20-30 V (28.3-42.4 Vp)
The limiting component (e.g. transformer, power supply or fuse) must be certified by
an NRTL (Nationally Recognized Testing Laboratory).
Pour les États-Unis et le Canada:
L’alimentation doit être limitée à :
a) max. 5 A pour des tensions de 0-20 V (0-28,3 Vp), ou
b) 100 VA pour des tensions de 20-30 V (28,3-42,4 Vp)
Le composant imposant la limite (par exemple, transformateur, alimentation élec-
trique ou fusible) doit être certifié par un NRTL (National Recognized Testing Labora-
tory, par exemple, UL).