background image

 

CARRIER ARM TOUCH TERMINAL 

ETT 7321 

 

29.10.2020 

Page 25 

05 

WATCHDOG 

The  program  was  interrupted  via  the 
watchdog logic. 

Possible Causes: 

User  program  interrupts  blocked 

over a longer period of time (STI 
command forgotten). 

Programming error in a hardware 

interrupt. 

INB, OUTB, INW, OUTW instruc-

tions used incorrectly.

 

The processor is defective. 

 

Solution: 

Correct programming error. 

Exchange CPU 

06 

GENERAL ERROR 

General error 

An error has occurred while stopping the 
application via the online interface. 

This error occurs only during the de-
velopment of the operating system. 

07 

PROM DEFECT 

An error has occurred while programming 
the memory module. 

Causes: 

The  program  memory  module  is 

defective. 

The user program is too large. 

The  program  memory  module  is 

missing. 

 

Solution: 

Exchange  the  program  memory 

module 

08 

RESET 

The  CPU  has  received  the  reset  signal 
and is waiting for further instructions. 

The user program is not processed. 

 

Info 

09 

WD DEFECT 

The  hardware  monitoring  circuit  (watch-
dog logic) is defective. 

After  power-up,  the  CPU  checks  the 
watchdog logic function. If an error occurs 
during this test, the CPU deliberately en-
ters an infinite loop from which no further 
instructions are accepted.

 

Solution: 

 Exchange CPU 

10 

STOP 

The  program  was  stopped  by  the  pro-
gramming system. 

 

11 

PROG BUSY 

Reserved 

 

12 

PROGRAM LENGTH 

Reserved 

 

13 

PROG END 

A memory module was successfully pro-
grammed. 

Info 

14 

PROG MEMO 

The  CPU  is  currently  programming  the 
memory module. 

Info 

Содержание ETT 7321

Страница 1: ...ETT 7321 Carrier Arm Touch Terminal Operating Manual Date of creation 29 10 2020 Version date 29 10 2020 Article number 01 230 7321 E...

Страница 2: ...rved No part of this work may be reproduced edited using an electronic system duplicated or dis tributed in any form print photocopy microfilm or in any other process without express permission We res...

Страница 3: ...A projective capacitive touch screen serves as the input medium for process data and pa rameters The output is shown on a 7 WVGA TFT color display With the LASAL visualization tool graphics can be cre...

Страница 4: ...es 6 2 1 Symbols Used 6 2 2 Disclaimer 8 2 3 General Safety Guidelines 9 2 4 Software Training 10 3 Norms and Guidelines 11 3 1 Guidelines 11 3 1 1 EU Declaration of Conformity 11 4 Technical Data 12...

Страница 5: ...e Connectors 17 6 Mechanical Dimensions 18 7 Assembly Installation 19 7 1 Check Contents of Delivery 19 7 2 Mounting Instructions 19 8 Wiring 20 8 1 Ground 20 8 2 Wiring 20 8 3 Shielding 21 8 4 ESD Pr...

Страница 6: ...leaning and Disinfecting the Touch Screen 34 14 2 Service 35 14 2 1 Calibrating the Touch Screen 35 14 3 Repair 35 15 Buffer Battery 36 15 1 Exchanging the Battery Option 1 37 15 2 Exchanging the Batt...

Страница 7: ...chnicians General knowledge of automation technology is required Further help and training information as well as the appropriate accessories can be found on our website www sigmatek automation com Ou...

Страница 8: ...s To avoid death or serious injuries observe all guidelines Avertissement d une situation dangereuse qui faute de prendre les mesures ad quates entra nera des blessures graves voire mortelles Respecte...

Страница 9: ...CARRIER ARM TOUCH TERMINAL ETT 7321 29 10 2020 Page 7 Danger for ESD sensitive components Les signes de danger pour les com posants sensibles aux d charges lectrostatiques...

Страница 10: ...machine operator is responsible for safe han dling as well as proper operation The current operating manual can be found on our website If necessary contact our support Subject to technical changes wh...

Страница 11: ...ssessment in accordance with machine guidelines 2006 42 EG before introducing a machine to the market Before commissioning this product check that conformance with the provi sions of the 2006 42 EG gu...

Страница 12: ...tware Training The application is created with the software LASAL CLASS 2 and LASAL SCREEN Editor Training for the LASAL development environment with which the product can be configured is provided In...

Страница 13: ...ation of Conformity The product ETT 7321 conforms to the following European guidelines 2014 35 EU Low voltage guideline 2014 30 EU Electromagnetic Compatibility EMC guideline 2011 65 EU Restricted use...

Страница 14: ...512 Mbyte NAND Flash Internal I O no Interfaces 1x USB 2 0 Type A 1x M12 connector supply and Ethernet Internal interface connections and devices 1x TFT LCD color display 1x touch screen Display Reso...

Страница 15: ...backlighting is on 2 Display technology with which display backlighting is used 3 The viewing angle is measured perpendicular to the display surface Due to the manufacturing process individual pixel e...

Страница 16: ...ooth operation with multitouch applications buttons and control elements that should be operated at the same time must have the minimum clearance shown below depending on the estimated touch point The...

Страница 17: ...ng conditions pollution degree 2 EMC resistance in accordance with EN 61000 6 2 industrial area EMC noise generation in accordance with EN 61000 6 4 industrial area Vibration resistance EN 60068 2 6 5...

Страница 18: ...ystem With such de vices Ethernet packets could be sent to the control with such a high fre quency i e broadcasts that the high interrupt load could cause a real time runtime error or runtime error By...

Страница 19: ...is can lead to device malfunctions It is also pos sible that these devices will not be detected at the USB port or function cor rectly Therefore it is recommended that every USB stick be tested before...

Страница 20: ...L Page 18 29 10 2020 6 Mechanical Dimensions Dimensions 183 6 x 138 8 x 46 45 mm W x H x D Material front 5 0 aluminum anodized black 1 mm hardened glass front with black frame cover sheet steel 1 mm...

Страница 21: ...e for damage If the device is damaged contact our customer service and do not install the device in your system Damaged components can disrupt or damage the system 7 2 Mounting Instructions The device...

Страница 22: ...nection to ground 8 2 Wiring The ETT 7321 is connected using the M12 connector The connector socket is documented in chapter 5 1 1 1 Turn off the current supply 2 Install the wiring Ensure the strands...

Страница 23: ...ETT 7321 29 10 2020 Page 21 8 3 Shielding It is recommended that the shielding be mounted at the entry point of the control cabinet housing Noise can then be deflected from the electronic components...

Страница 24: ...roduct the potential with ground must be equalized by touching the control cabinet or ground terminal Electrostatic loads through clothing or shoes can be thereby dissipated 8 5 USB Interface Connecti...

Страница 25: ...CARRIER ARM TOUCH TERMINAL ETT 7321 29 10 2020 Page 23 10 Process Diagram...

Страница 26: ...e maximum time the time can be configured using 2 system variables Runtime Remaining time SWRuntime Preset value for runtime counter Optimize the application s cyclic task Use higher capacity CPU Conf...

Страница 27: ...memory module Causes The program memory module is defective The user program is too large The program memory module is missing Solution Exchange the program memory module 08 RESET The CPU has receive...

Страница 28: ...The program is stopped and the CPU is currently receiving a new module or pro ject Info 21 INVALID MODULE The CPU has received a module that does not belong to the project Solution Recompile and down...

Страница 29: ...Use the correct operating system version 35 MAX IO Reserved 36 MODULE LOAD ERROR The LASAL Module or project cannot be loaded Solution Recompile and download the en tire project 37 BOOTIMAGE FAIL URE...

Страница 30: ...has occurred during a floating point operation 60 DIAS RISC ERROR Error from the Intelligent DIAS Master Restart report error to SIGMATEK 64 INTERNAL ERROR An internal error has occurred all appli ca...

Страница 31: ...es SRAM configured incorrectly Battery for powering the internal program memory is empty Solution Analyze log file Event00 log Event19 log Check configuration Exchange battery for powering the interna...

Страница 32: ..._FILE_OPEN An attempt was made to open an unknown table 114 C_OUTOF_NEAR Memory allocation failed 115 C_OUT OF_FAR Memory allocation failed 116 C_INCOMAPTIBLE An object with the same name already exis...

Страница 33: ...CARRIER ARM TOUCH TERMINAL ETT 7321 29 10 2020 Page 31 252 CONTINUE 253 PRERUN The application is started 254 PRERESET The application is ended 255 CONNECTION BREAK...

Страница 34: ...igh mechanical stress must therefore be avoided For storage and transport the same values for humidity and vibration as for operation must be maintained During transport temperature and humidity fluct...

Страница 35: ...age 33 13 Storage When not in use store the operating panel according to the storage condi tions See chapter 12 During storage ensure that all protective covers are placed correctly so that no contami...

Страница 36: ...is recommended To avoid fluids cleaning solutions from getting into the housing the device must not be sprayed directly To clean no erosive cleaning solutions chemicals abrasive cleansers or hard obje...

Страница 37: ...be achieved via the CLI command or the application if the application engineer has provided the option calib 14 3 Repair When sent for repair the panel should be transported in the original packag ing...

Страница 38: ...battery be replaced every 8 years to ensure optimal per formance COMPANY DATA Lithium battery RENATA 3 0 V 235 mAh Battery order number 01 690 055 Use type CR2032 batteries from RENATA only Disconnect...

Страница 39: ...cover with a TX8 Torx screwdriver 3 Remove the battery cover When exchanging the battery caution must be taken to avoid a short circuit since it could cause a defect in the terminal 4 Using the strap...

Страница 40: ...device supply 3 Remove the locking screws in the battery cover with a TX8 Torx screwdriver 4 Remove the battery cover When exchanging the battery caution must be taken to avoid a short circuit since...

Страница 41: ...es after the screen has been turned off for some time or when dynamic content is displayed damage from the permanent effect is irreversible This effect can have the following causes Operation without...

Страница 42: ...CARRIER ARM TOUCH TERMINAL Page 40 29 10 2020 17 Disposal Should you need to dispose of the device the national electronic scrap regulation must be observed The panel cannot be discarded with domesti...

Страница 43: ...CARRIER ARM TOUCH TERMINAL ETT 7321 29 10 2020 Page 41 18 Accessories 18 1 Cable See documentation for operating device connection cables...

Страница 44: ...ETT 7321 CARRIER ARM TOUCH TERMINAL Page 42 29 10 2020 Documentation Changes Change date Affected page s Chapter Note...

Отзывы: