BUILD-IN TERMINAL TOUCH
ETT 731
05.12.2019
Page 5
1.2
Electrical Requirements
Supply voltage
typ24 V DC (+18-30 V DC)
Current consumption of power
supply at +24 V
typically 210 mA
(without externally connected devices)
maximum 360 mA
(with externally connected devices)
Current consumption of
standby voltage at +24 V
typically 110 mA
(without externally connected devices)
maximum 180 mA
(with externally connected devices)
Inrush current
600 mA (1 ms)
UL standard
for UL
(1)
: must be supplied with SELV / PELV and Limited Energy
Digital output also is SELV / Limited Energy.
(1)
In US according to Class 2 UL 1310 or UL 61010-1, 3
rd
edition, chapter 9.4 or LPS (limited power supply)
UL 60950-1 or Limited Energy UL 1585
1.3
Terminal
Dimensions
180 x 135 x 40.9 mm (W x H x D)
Material
front plate: 3 mm aluminum, black anodized
Weight
circa 600 g
1.4
Environmental Conditions
Storage temperature
-
10 … +80 °C
Environmental temperature
0 … +60 °C
Humidity
10-90 %, non-condensing
Operating conditions
Pollution degree 2
indoor use
altitude up to 2000 m
EMC stability
in accordance with product standard EN 60730-1
Vibration tolerance
EN60068-2-6
2
… 9 Hz: amplitude 3.5 mm
9
… 200 Hz: 1 g (10 m/s²)
Shock resistance
EN60068-2-27
15 g (150 m/s²)
duration 11 ms, 18 Shocks
Protection type
EN 60529
protection through housing
front: IP54 (no UL-rating)
cover: IP20 (no UL-rating)
Содержание ETT 731
Страница 9: ...BUILD IN TERMINAL TOUCH ETT 731 05 12 2019 Page 7 2 Mechanical Dimensions...
Страница 15: ...BUILD IN TERMINAL TOUCH ETT 731 05 12 2019 Page 13 A mounting position of 60 to 120 is also required...
Страница 24: ...ETT 731 BUILD IN TERMINAL TOUCH Page 22 05 12 2019 10 Process Diagram...
Страница 36: ...ETT 731 BUILD IN TERMINAL TOUCH Page 34 05 12 2019...