28
Copyright 2018, SIGMAKOKI Co.,Ltd.
『
『
『
『
Point of view about INPOSITION range
』
』
』
』
In the conition of closed loop control, a positioning of stage is completed when a reading of scale reaches inside a
range of INPOS. And Setting value of 1~99 is based on 1 pulse resolution from glass scale.
*) Regarding to Scale resolution, it depends on each stage, so please refer to sensor resolution in each stage.
<Example>
In case of sensor resolution 0.01
µ
m
Setting Value=1: INPOS range is 1×±0.01
µ
m=±0.01
µ
m
Setting Value=99: INPOS range is 99×±0.01
µ
m=±0.99
µ
m
17
~
24) RES_UNIT 0
~
7: Scale setting
Set Scale resolution and direction.
[Setting Range]
-30000
~
30000
:
- input is reverse direction. Unit is nm.
Reference:
Stage
RES_UNIT
OSMS(CS)20
500
OSMS(CS)26
500
OSMS(CS)33
500
HST(GS)-50
50
HST(GS)-100
50
HST(GS)-200
50