11
Factory Programming
Resetting the factory settings is done when the siren is in a standby mode. To restore the factory
settings, simultaneously press the MENU and SELECT buttons for three seconds until you hear the
confirmation signal (five BEEP). Then the LEDs with
“SOUND”
and
“5-24”
indication will flash for
one second and the siren will return to Standby mode.
Selecting the Foam detector function (Only in IRIS PLUS FSD)
Exit Setup
As soon the LEDs
“FLASH” & “L/S” & “Hi-Lo”
, light, press “SELECT” button to select if the foam
detector will be active or inactive. Every time you press “SELECT” button, will increase or decrease
the brightness of the three LEDs. When the LEDs have a low brightness, the foam detector will be
deactivated and when the light level is high the foam detector will be activated.
Press “MENU” button to save your setting and navigate to next selection. The LED
“SOUND”
,
will light to indicate you are in the first step of setup.
To store this setting into memory, and navigate to the next menu, press the MENU button.
The LEDs with the indication
“FLASH” & “L/S
&
“Hi-Lo”
, will turn on.
To exit setup press continuously “MENU” button until you hear the confirmation sound (5 BEEPs).
Immediately, the LEDs
“SOUND” & “5-24”
will turn on for 1 second and the siren will enter
standby mode.
Note
Also, the siren exits programming and returns to standby mode, after three minutes
without pressing any of the two buttons.
This function allows you to open the siren for maintenance or to change the battery without the
siren being activated by the tamper. A prerequisite is that the “TC” input of the siren has been
connected to the panel, as described in the chapter on Selecting the siren’s Operation Mode, in
the section “Bypassing the Siren’s Tamper - Removing the Lid”.
Whenever you wish to open the siren when it is installed and connected to the Alarm panel, follow
the procedure below:
As soon as you have connected the siren’s TC to the corresponding output of the panel,
activate the corresponding PGM of the panel or, in the case of a Sigma panel, arm and
immediately disarm the panel to apply + 12V to the TC input. When you do the above, you have
ten minutes to open the siren lid without activating an alarm, because Tamper is inactive for
that period. After opening the lid, the time that the siren may remain open becomes unlimited
and is reset when the siren lid is closed again.
Upon completing service, close the lid and secure it with the corresponding screws. As soon as
you close the lid, the two siren LEDs will light for five seconds, and when a minute has elapsed
since you close it, the siren will return to normal operation and Tamper will be active again.
Also, for security reasons, siren’s Tamper is always active, as soon as 10 minutes have elapsed
since the voltage is applied to the TC, without opening the lid.
Opening the siren (Engineer Mode)