Status: alarm 1
Bit 3 and 2
Alarm status of 1st -
Parameter (Y1 value)
11 : Hi alarm
01 : Lo alarm
00 : No alarm
Status: alarm 2
Bit 1 and 0
Alarm status of 2nd -
Parameter (Y2 value)
11 : Hi alarm
01 : Lo alarm
00 : No alarm
1st - Parameter
2
all
Uint16
Y1 value: Level (x
0.1%)
Y1 is calculated
based on Y2 value by
the formula:
Y1 = Y2*a1+b1
2nd - parameter
2
all
Uint16
Y2 value:
Distance(mm)
Using the configuration cable to connect to the sensor as below picture.
During connection with Modbus configuration tool, the Sigfox node will send all data in realtime: Battery, Battery level,
Vref, Button status, reed switch status, PCB temperature, Measured value, alarm status.
Step to configure & check data:
Step 1: Install the Modbus Configurator Software in the link below
https://filerun.daviteq.com/wl/?id=qK0PGNbY1g1fuxTqbFW9SXtEvCw7bpc6
6. Offline configuration
Serial port configuration on computer: 9600 baud, None parity, 1 stop bit.
Reading data by Function 3.
Writing data by Function 16.
NOTE:
The Modbus configuration can be done in the first
60s
after power up the Sigfox node. After 60s, if user can not
finish the configuration, user need to reset the power of Sigfox node again, by removing battery in at least 15s.