6.1 Pre-selectable limit checks (Go / No-Go option)

An acoustic signal can be generated when the measured value of 
resistance falls below an adjustable noGo value.
A  separate  noGo  value  can  be  set  for  each  range  of  insulation 
resistance measurement as well as for Ohms, Continuity ranges. 
Refer to the “11. Menu structure” section for how to set the value 
for the noGo value.

6.2

Storing the measured resistance value

l

To  store  the  value  of  resistance  press  “STORE”  key  when  the 
resistance  measurement  is  in  progress.  This  will  store  the 
resistance measured at the instant the key is pressed.

l

This way maximum 10 readings per range can be stored.

th

l

After 10 values are stored for the selected range the 11  value when 
stored will over-write the first value i.e. at any given point of time 
only ten readings per range can be stored.

l

The readings are stored in a volatile memory. Therefore when the 
instrument is switched off, the readings are lost.

Recalling the stored values

The  stored  values  can  be  recalled  and  viewed  in  the  menu 
structure.
Refer to the “11. Menu Structure” section for how to view the stored 
value.

6.3

Minimum  value  and  Maximum  value  “MIN/MAX”  storage 
facility (for all measuring ranges)

With  the  MIN/MAX  function,  you  can  hold  the  minimum  and  the 
maximum  measured  value  which  was  applied  to  the  input  of  the 
instrument after activating MIN/MAX. The most important application is 
determination  of  minimum  and  the  maximum  value  for  long  term 
monitoring of measured quantities.
The function MIN/MAX can be activated in all measuring ranges.
MIN/MAX  does  not  influence  analog  indication,  you  can  still  read  the   
actual measured value.

Apply the measured quantity to instrument prior to activating MIN/MAX 
function.

The MIN/MAX function is switched off when.
1.

        Key is pressed for approximately for 1 Sec.  OR

2. Then function selector switch is operated   OR
3. When the instrument is turned OFF and ON again

9

Function

MIN/MAX

Measured Value

MIN and MAX

Meter reaction

Display

Measured value Digital MIN/MAX

Sound

signal

1. Activate
    and store
2. Store
    and display

3. Return
    to 1.

Reset

short

short

short

short

long

Stored

Stored continued
in background
new MIN and MAX
values are displayed
Same as 1.

Stored values are

not cleared

Cleared

Actual measured value

Stored MIN value

Stored MAX value

Same as 1.

Cleared

MIN/MAX

flash

MIN flash

MAX flash

Same as 1.

Cleared

1x

1x

1x

1x

2x

12

8.

 

Voltage

 

Measurement

 

(V

 

AC/DC)

You can use this instrument for voltage measurement from 25V  to 600V 
AC or DC.
*

Keep the function selector switch to “V     ” position and
apply the input.

*

The instrument automatically displays whether the input
is AC or DC along with the value of the external voltage.

*

If the value of voltage is < 25V (AC or DC), the display
“025V” flashes. If the value of  the voltage is > 600V (AC
or DC), a continuos acoustic signal is generated.

*

When reverse DC is applied it displays “-dc”

Additional features available in Insulation measurement ranges.

1.

Minium and Maximum value “MIN/MAX” storage

Voltage Measurement

9.

Default

 

Live

 

Circuit

 

Warning

When  more  than  25V  (AC  or  DC)  is  applied  to  the  terminals  the 
instrument defaults to voltmeter on all switch positions. In addition the 
beeper will sound on all switch position (except the V      position).

When external voltage>25 V is present, Insulation Ohm and Continuity 
Tests are inhibited.

When external voltage <25 V is present, only the Insulation Tests are 
available !!

Note : 

The default live circuit warning does not operate 

(i) when in STOPWATCH mode.
(ii) when in MENU structure.

+(-)/~

-(+)/~

2 9

2

M

W

50V

100V

250V

500V

1KV

V

Zeta 20

400

100kM

600

10kM

200
1MG

800
1kM

100k

1000

10MG

8

L

L

VAC VDC

CE

Содержание Zeta 20

Страница 1: ... Central Buildings Woodland Close Old Woods Trading Estate Torquey Devan England TQ27BB Website www sifamtinsley com uk Contact Number 44 O 1803 615139 E mail info tinsley co uk Sifam Tinsley Instrumentation 3105 Creekside Village Drive Suite No 801 Kennesaw Georgia 30144 Contact Number 1 404 736 4903 Web www sifamtinsley com P R E C I S I O N I N S T R U M E N T A T I O N ...

Страница 2: ......

Страница 3: ...mplete warranty card is not presented to authorised person at the time ofrepairs 3 Meter accessories is not used as per the instructions in the instruction manual 4 Defect caused by misuse negligence accidents tampering and Acts of God 5 Improperrepairingbyanypersonnotauthorisedbythecompany 6 Modification Alterationofanysortismadeinelectricalcircuitry 7 Sealprovidedinside outsideisbroken Warranty ...

Страница 4: ...aking capacity of 10kA Recommended fuse manufacturer Siba Part No 70 065 63 0 5A Be absolutely sure that only the specified fuses are used The use of a fuse with different triggering characteristics a different nominal current or a different breaking capacity exposes the operator the system and the measuring instrument to danger The use of repaired fuses or short circuiting of the fuse holder is p...

Страница 5: ...3 Fuses 19 13 4 Housing 19 Ω Mechanical Design Protection Instrument IP50 For terminal socket IP20 according to DIN VDE 0470 Part 1 EN60529 Dimensions W x H x D 84mm x 195 mm x 35 mm Weight 500 g including battery 13 Maintenance Attention Disconnect the instrument from the measuring circuit before opening the instrument to replace the battery or the fuse 13 1 Battery Before initial Start up or aft...

Страница 6: ...connecting test leads Test leads and crocodile clips must be in good condition clean and with no broken or cracked insulation Meaning of symbols on the instrument u 4 Warning concerning a point of danger Attention observe documentation Earth Continuous doubled or reinforced insulation EU Conformity Mark 17 Power Supply Battery 6 x 1 5V cells IEC Lr6 Alkaline Manganese rechargeable cells provided i...

Страница 7: ...sing the ON OFF button 2 By changing the function selector switch from current position to desired function Switch on is acknowledged by a sound signal The instrument is now ready for operation Attention Before opening disconnect the instrument from the measuring circuit and ensure high voltage is not available on leads Automatic turn off Your instrument turn off automatically if any of the keys o...

Страница 8: ...0 00 Manual 0 00 0 00 0 00 0 00 0 00 0 00 0 00 12 Specifications Meas Range Resolu Accuracy Overload function tion of rdg value and digit duration 1 For insulation resistance range 2 For low Ohms continuity Ranges Terminal voltage on open Open circuit voltage circuit DC 5V 1V d c 0 to 30 of rated voltage Lead resistance Short circuit current 2 mA compensation 0 9 99 W Test current on load 1 mAat m...

Страница 9: ... key Note The instrument s batteries are depleted during insulation resistance measurement Only press and hold the TEST key as long as it is necessary to take the reading in the manual measurement mode Continuous measurement as described below should be performed if absolutely necessary 7 14 11 1 Description of Menu Items 11 1 1 Setting Backlit OFF ON at all ranges Basic OFF ON Display 1 Now scrol...

Страница 10: ...t continues for the pre determined time Pre selectable time 10 sec 5 min Refer to the 11 Menu structure section for how to set the value for pre selectable time Once the time is set it is applicable to all the 5 ranges of Insulation measurement n Select the required value of the time for which the test is carried out n BrieflyPresstheTESTkey Theinsulationresistancetestcarries on for the time inter...

Страница 11: ...g MIN MAX function The MIN MAX function is switched off when 1 Key is pressed for approximately for 1 Sec OR 2 Then function selector switch is operated OR 3 When the instrument is turned OFF and ON again 9 Function MIN MAX Measured Value MIN and MAX Meter reaction Display Measured value Digital MIN MAX Sound signal 1 Activate and store 2 Store and display 3 Return to 1 Reset short short short sho...

Страница 12: ...alue Default value is 0W Refer to the 11 Menu structure section for how to set the value for the limit value 7 3 Zero adjustment When measuring very low resistance values you can eliminate resistance of leads and contact resistance by zero adjustment Connect the test leads to instrument and connect the free ends of the leads to one another Wait for reading to stabilize Briefly press the TEST push ...

Отзывы: