NP40 Power Quality Analyzer
User’s Guide
Power and energy
Measurement range
Resolution
Accuracy
Active power
P(kW)
,
apparent power
S(kVA)
,
1.0~20.00MW
0.1kW
±1.5±10 characters
reactive power
Q(kvar)
,
Kilowatt-hour
0.00kWh~200GWh
10Wh
±1.5±10 characters
Power factor (TPF)
0~1
0.01
±0.03
Cos (DPF)
0~1
0.01
±0.03
Tg (tanØ)
-10...10
0.01
±3%
Flicker
Measurement range
Resolution
Accuracy
Flicker severity (Pst,
0.00~20.00
0.01
Within ±5% of table
Plt) and t
he
value according to
instantaneous flicker
IEC61000-4-15
sensation level
Unbalance
Measurement range
Resolution
Accuracy
Voltage unbalance
0.0~5.0%
0.1%
±0.5%
Current unbalance
0.0~20.0%
0.1%
±1%
Voltage phase
-360°~ 0°
1°
±2 characters
Current phase
-360°~ 0°
1°
±5 characters
Rapid range of
Measurement range
Resolution
Accuracy
voltage
Voltage
Vpk
±6000Vpk
1V
±15%
Vrms
10~1000Vrms
1V
±2.5%
Minimum test time
50 s
Sampling rate
20kS/s
Inrush current
Measurement range
Resolution
Accuracy
Arms
0~3000Arms
0.1
±1%±5 characters
Inrush evaluation
6s~32min settable
10ms
±20ms
time